9440500990 Rev D 251
DECS-250N PROFIBUS Communication
Instance Name
Inst. #
Type
RW
Key Name
Unit
Range
Control Panel Status
30
UINT8
R
DECSCONTROL DECS
PREPOSITION 2 ACTIVE
Active setpoint is not at pre-
position 2 value=0, Active setpoint
is at pre-position 2 value=1
Control Panel Status
30
UINT8
R
DECSCONTROL DECS
PREPOSITION 3 ACTIVE
Active setpoint is not at pre-
position 3 value=0, Active setpoint
is at pre-position 3 value=1
Control Panel Status
30
UINT8
R
VIRTUALSWITCH
VIRTUALSWITCH1
Open=0, Closed=1
Control Panel Status
30
UINT8
R
VIRTUALSWITCH
VIRTUALSWITCH2
Open=0, Closed=1
Control Panel Status
30
UINT8
R
VIRTUALSWITCH
VIRTUALSWITCH3
Open=0, Closed=1
Control Panel Status
30
UINT8
R
VIRTUALSWITCH
VIRTUALSWITCH4
Open=0, Closed=1
Control Panel Status
30
UINT8
R
VIRTUALSWITCH
VIRTUALSWITCH5
Open=0, Closed=1
Control Panel Status
30
UINT8
R
VIRTUALSWITCH
VIRTUALSWITCH6
Open=0, Closed=1
Control Panel Status
30
UINT8
R
ALARMREPORT
ALARMOUTPUT
No active alarms=0, Active
alarms=1
Control Panel Status
30
UINT8
R
DECSPSSMETER DECS
PSS ACTIVE
PSS not active=0, PSS active=1
Control Panel Status
30
UINT8
R
DECSCONTROL DECS
NULL BALANCE
Not active=0, Active=1
System Status
31
UINT8
R
ALARMS OEL ALM
Not active=0, Active=1
System Status
31
UINT8
R
ALARMS UEL ALM
Not active=0, Active=1
System Status
31
UINT8
R
ALARMS SCL ALM
Not active=0, Active=1
System Status
31
UINT8
R
ALARMS VAR LIMITER
ACTIVE
Not active=0, Active=1
System Status
31
UINT8
R
ALARMS VOLTAGE
MATCHING ACTIVE
Not active=0, Active=1
System Status
31
UINT8
R
DECSCONTROL DECS
SOFT START SELECT
SECONDARY SETTINGS
Primary settings active=0,
Secondary settings active=1
System Status
31
UINT8
R
DECSCONTROL DECS PSS
SELECT SECONDARY
SETTINGS
Primary settings active=0,
Secondary settings active=1
System Status
31
UINT8
R
DECSCONTROL DECS OEL
SELECT SECONDARY
SETTINGS
Primary settings active=0,
Secondary settings active=1
System Status
31
UINT8
R
DECSCONTROL DECS UEL
SELECT SECONDARY
SETTINGS
Primary settings active=0,
Secondary settings active=1
System Status
31
UINT8
R
DECSCONTROL DECS SCL
SELECT SECONDARY
SETTINGS
Primary settings active=0,
Secondary settings active=1
System Status
31
UINT8
R
DECSCONTROL DECS
PROTECT
SELECT SECONDARY
SETTINGS
Primary settings active=0,
Secondary settings active=1
System Status
31
UINT8
R
DECSCONTROL DECS PID
SELECT SECONDARY
SETTINGS
Primary settings active=0,
Secondary settings active=1
System Status
31
UINT8
R
DECSCONTROL DECS VAR
LIMITER SELECT
SECONDARY SETTINGS
Primary settings active=0,
Secondary settings active=1
System Status
31
UINT8
R
DECSCONTROL DECS
PREPOSITION
Active setpoint is not at a pre-
position value=0, Active setpoint is
at a pre-position value=1
System Status
31
UINT8
R
DECSCONTROL DECS VAR
CONTROLLER ACTIVE
VAR not active=0, VAR active=1
System Status
31
UINT8
R
DECSCONTROL DECS PF
CONTROLLER ACTIVE
PF not active=0, PF active=1