Event Recorder DECS-250N
Level Triggers
Level triggering initiates a data log based on the value of an internal variable. The variable can be a
minimum or maximum value and can be specified to trigger a record when the monitored variable crosses
a minimum threshold from above, or a maximum threshold from below. A minimum and maximum
threshold may also be selected for the monitored variable, causing the monitored value to trigger a record
when it rises above its maximum threshold or decreases below its minimum threshold.
Level triggers are configured in BESTCOMSPlus on the Level Triggers tab (Figure 82) in the Data Log
area of the Report Configuration. The Level Triggers tab consists of a list of parameters that can be
selected to trigger a data log. Each parameter has a level trigger enable setting which configures
triggering of a data log when the parameter increases above the upper threshold setting or decreases
below the lower threshold setting. The parameters available to trigger a data log are listed below.
Figure 82. Data Log Level Triggers
Auxiliary voltage input
AVR output
AVR PID error signal input
Bus frequency
Bus voltage
Comp. frequency deviation
Control output
Cross current input
Droop
FCR error
FCR output
FCR state
Field current
Field voltage
Frequency response
FVR error
FVR output
FVR state
Generator apparent power
Generator average current
Generator average voltage
Generator current Ia
Generator current Ib
Generator current Ic
Generator frequency
Generator power factor
Generator reactive power
Generator real power
Generator voltage Vab
Generator voltage Vbc
Generator voltage Vca
Negative sequence current
Negative sequence voltage
Null balanced level
OEL controller output
OEL ref.
OEL state
Internal state
Position indication
Positive sequence current
Positive sequence voltage
PSS electrical power
PSS filtered mech. power
PSS final output
PSS lead/lag #1
PSS lead/lag #2
PSS lead/lag #3
PSS lead/lag #4
PSS mechanical power
PSS mechanical power LP #1
PSS mechanical power LP #2
PSS mechanical power LP #3
PSS mechanical power LP #4
PSS post-limit output