Basler-electric DECS-250N User Manual Page 158

  • Download
  • Add to my manuals
  • Print
  • Page
    / 370
  • Table of contents
  • TROUBLESHOOTING
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 157
142 9440500990 Rev D
BESTlogicPlus DECS-250N
Name Description Symbol
Gen Breaker Fail
to Open
The generator breaker did not open in the close
wait time period. (Available when the controller is
equipped with the optional Auto synchronizer, style
number xxxxAxx)
Gen Breaker Fail
to Close
The generator breaker did not close in the close
wait time period. (Available when the controller is
equipped with the optional Auto synchronizer, style
number xxxxAxx)
Gen Breaker
Sync Fail
True when generator breaker sync has failed.
(Available when the controller is equipped with the
optional Auto synchronizer, style number xxxxAxx)
Gen Dead True when the Generator Breaker Dead condition
settings have been exceeded. (Available when the
controller is equipped with the optional Auto
synchronizer, style number xxxxAxx)
Gen Failed True when the Generator Breaker Stable condition
settings are not met. (Available when the controller
is equipped with the optional Auto synchronizer,
style number xxxxAxx)
Gen Stable True when the Generator Breaker Stable condition
settings have been exceeded. (Available when the
controller is equipped with the optional Auto
synchronizer, style number xxxxAxx)
GOV Contact
Type Proportional
True when this option is selected. (Governor Bias
Control Settings screen)
Internal Tracking
Active
True when internal tracking is running.
IRIG Sync Lost True when IRIG signal is not being received.
Manual Mode
Active
True when the unit is in Manual mode (FCR/FVR).
Network Load
Share Active
True when network load sharing is active.
Network Load
Share Config
Mismatch
True when the unit’s configuration does not match
the configuration of the other units with load
sharing enabled.
Network Load
Share ID Missing
True when any of the load sharing enabled units
are not detected on the network.
Network Load
Share Receiving
ID 1 - 16
True when data is being received from a specific
unit on the load share network.
No Network Load
Share Data
Received
True when Network Load Sharing is enabled but
there is no data being received from other network
load sharing devices.
Network Load
Share Status 1-4
This element functions in conjunction with the
Network Load Share Broadcast elements on all
units on the network. True when the corresponding
Network Load Share Broadcast element input is
true on another unit on the network.
Page view 157
1 2 ... 153 154 155 156 157 158 159 160 161 162 163 ... 369 370