Protection DECS-250N
Figure 41. Configurable Protection Settings
A
Label Text: Accepts a maximum of 16 alphanumeric characters.
B
Param Selection: Select Gen VAB, Gen VBC, Gen VCA, Gen V Average, Bus Freq, Bus VAB, Bus VBC,
Bus VCA, Gen Freq, Gen PF, KWH, kvarh, Gen IA, Gen IB, Gen IC, Gen I Average, KW Total, KVA Total,
kvar Total, EDM Ripple, Exciter Field Voltage, Exciter Field Current, Auxiliary Input Voltage, Auxiliary
Input Current (mA), Setpoint Position, Tracking Error, Negative Sequence Voltage, Negative Sequence
Current, Positive Sequence Voltage, Positive Sequence Current, PSS Output, Analog Input 1, Analog
Input 2, Analog Input 3, Analog Input 4, Analog Input 5, Analog Input 6, Analog Input 7, Analog Input 8,
RTD Input 1, RTD Input 2, RTD Input 3, RTD Input 4, RTD Input 5, RTD Input 6, RTD Input 7, RTD Input
8, Thermocouple 1, Thermocouple 2, Power Input, or NLS Error Percent.
C
Stop Mode Inhibit: Select Yes or No.
D
Arming Delay: Adjustable from 0 to 300 seconds in 1 second increments.
E
Hysteresis: Adjustable from 0 to 100% of the threshold setting in 0.1% increments.
F
Mode: Select Over, Under, or Disabled.
G
Threshold: Adjustable from 999,999 to +999,999 in 0.01 increments.
H
Activation Delay (s): Adjustable from 0 to 300 seconds in 1 second increments.