9440500990 Rev D 227
DECS-250N Modbus™ Communication
Name
Register
Type
Bytes
R/W
Unit
Range
Droop Value
42280
Float
4
R W
Percent
0 - 30
L-Drop Value
42282
Float
4
R W
Percent
0 - 30
Auxiliary Limit Enable
42284
Int32
4
R W
n/a
Disabled=0 Enabled=1
Field Current Regulation Pre-position
Mode 3
42286
Uint32
4
R W
n/a
Maintain=0 Release=1
Field Current Regulation Pre-position 3
42288
Float
4
R W
Amp
Setpoint adjustment range determined
by registers 42212 and 42214.
Generator Voltage Pre-position Mode 3
42290
Uint32
4
R W
n/a
Maintain=0 Release=1
Generator Voltage Pre-position 3
42292
Float
4
R W
Volt
Setpoint adjustment range determined
by registers 42228 and 42230.
Generator var Pre-position Mode 3
42294
Uint32
4
R W
n/a
Maintain=0 Release=1
Generator var Pre-position 3
42296
Float
4
R W
kilovar
Setpoint adjustment range determined
by registers 42244 and 42246.
Generator PF Pre-position Mode 3
42298
Uint32
4
R W
n/a
Maintain=0 Release=1
Generator PF Pre-position 3
42300
Float
4
R W
Power Factor
Setpoint adjustment range determined
by registers 42260 and 42262.
FVR Pre-position Mode 3
42302
Uint32
4
R W
n/a
Maintain=0 Release=1
FVR Pre-position 3
42304
Float
4
R W
Volt
Setpoint adjustment range determined
by registers 42276 and 42278.
Active Field Current Regulation Setpoint
42306
Float
4
R W
Amp
Setpoint adjustment range determined
by registers 42212 and 42214.
Active Generator Voltage Setpoint
42308
Float
4
R W
Volt
Setpoint adjustment range determined
by registers 42228 and 42230.
When the With Limits box is checked on
the Auxiliary Input screen in
BESTCOMSPlus, register 42308 equals
register 42216 plus the Aux input.
When the With Limits box is not
checked on the Auxiliary Input screen in
BESTCOMSPlus, register 42308 equals
register 42216.
Active Generator var Setpoint
42310
Float
4
R W
kilovar
Setpoint adjustment range determined
by registers 42244 and 42246.
Active Generator PF Setpoint
42312
Float
4
R W
Power Factor
Setpoint adjustment range determined
by registers 42260 and 42262.
Active FVR Setpoint
42314
Float
4
R W
Volt
Setpoint adjustment range determined
by registers 42276 and 42278.
Transient Boost Enable
42316
Int32
4
R W
n/a
Disabled=0,Enabled=1
Transient Boost, Fault Voltage
Threshold
42318
Float
4
R W
Percent
0 100
Transient Boost, Fault Current
Threshold
42320
Float
4
R W
Percent
0 400
Transient Boost, Minimum Fault
Duration
42322
Float
4
R W
Second
0 – 1
Transient Boost, Voltage Setpoint
Boosting Level
42324
Float
4
R W
Percent
0 100
Transient Boost, Clearing Voltage
Threshold
42326
Float
4
R W
Percent
0 50
Transient Boost, Clearing Voltage Delay
42328
Float
4
R W
Second
0 – 1
Global Settings
Table 30. Global Settings Group Parameters
Group
Name
Register
Type
Bytes
R/W
Unit
Range
PLC Timed Element Settings
Logic Timer 1 Output Timeout
42400
Float
4
R W
Sec
0 - 1800
PLC Timed Element Settings
Logic Timer 2 Output Timeout
42402
Float
4
R W
Sec
0 - 1800
PLC Timed Element Settings
Logic Timer 3 Output Timeout
42404
Float
4
R W
Sec
0 - 1800
PLC Timed Element Settings
Logic Timer 4 Output Timeout
42406
Float
4
R W
Sec
0 - 1800
PLC Timed Element Settings
Logic Timer 5 Output Timeout
42408
Float
4
R W
Sec
0 - 1800
PLC Timed Element Settings
Logic Timer 6 Output Timeout
42410
Float
4
R W
Sec
0 - 1800