DECS-250N Limiters
Figure 49. UEL Custom Curve Screen
A
UEL Configuration Enable: Check box to enable underexcitation limiter.
B
Curve Selection: Select Internal or Customized.
C
Internal Curve: Enter number to adjust range of y axis.
D
Custom Curve: Insert, enter, and delete curve data points as needed.
E
Real Power Exponent: Enter a value of 1 or 2.
F
Real Power Filter Time Constant: Enter a value from 0 to 20 seconds in 0.1 second increments.
Stator Current Limiter
BESTCOMSPlus Navigation Path: Settings Explorer, Operating Settings, Limiters, SCL
HMI Navigation Path: Settings, Operating Settings, Limiters, SCL
The stator current limiter (SCL) monitors the level of stator current and limits it to prevent stator
overheating. To limit the stator current, the SCL modifies the excitation level according to the direction of
var flow into or out of the generator. Excessive stator current with leading power factor calls for increased
excitation. Excessive stator current with lagging power factor calls for reduced excitation.
The SCL can be enabled
A
in all regulation modes. When operating in Manual mode, the DECS-250N will
announce high stator current but will not act to limit it. Primary and secondary SCR setting groups provide
additional control for two distinct machine operating conditions. Stator current limiting is provided at two
levels: low and high (see Figure 50). SCL settings are illustrated in Figure 51.