Basler-electric DECS-250N User Manual Page 277

  • Download
  • Add to my manuals
  • Print
  • Page
    / 370
  • Table of contents
  • TROUBLESHOOTING
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 276
9440500990 Rev D 261
DECS-250N PROFIBUS Communication
Instance Name
Inst. #
Type
RW
Key Name
Unit
Range
FVR Setpoints
72
Float
R/W
Exc Vol Setpoint GG
V
0 - 75
FVR Setpoints
72
Float
R/W
Exc Vol Min Setpoint
Limit GG
%
0 - 150
FVR Setpoints
72
Float
R/W
Exc Vol Max Setpoint
Limit GG
%
0 - 150
FVR Setpoints
72
Float
R/W
Exc Vol
Preposition1 GG
V
0 - 75
FVR Setpoints
72
Float
R/W
Exc Vol
Preposition2 GG
V
0 - 75
FVR Setpoints
72
Float
R/W
Exc Vol
Preposition3 GG
V
0 - 75
VAR Setpoints
73
UINT32
R/W
Gen Var Prepos
Mode1 GG
No
Unit
Maintain=0 Release=1
VAR Setpoints
73
UINT32
R/W
Gen Var Prepos
Mode2 GG
No
Unit
Maintain=0 Release=1
VAR Setpoints
73
UINT32
R/W
Gen Var Prepos
Mode3 GG
No
Unit
Maintain=0 Release=1
VAR Setpoints
74
Float
R/W
Sys Option Fine Adjust
Band GG
%
0 - 30
VAR Setpoints
74
Float
R/W
Gen Var Traverse
Rate GG
Sec
10 - 200
VAR Setpoints
74
Float
R/W
Gen Var Setpoint GG
kvar
0 41.57
VAR Setpoints
74
Float
R/W
Gen Var Min Setpoint
Limit GG
%
-100 - 100
VAR Setpoints
74
Float
R/W
Gen Var Max Setpoint
Limit GG
%
-100 - 100
VAR Setpoints
74
Float
R/W
Gen Var
Preposition1 GG
kvar
0 41.57
VAR Setpoints
74
Float
R/W
Gen Var
Preposition2 GG
kvar
0 41.57
VAR Setpoints
74
Float
R/W
Gen Var
Preposition3 GG
kvar
0 41.57
PF Setpoints
75
UINT32
R/W
Gen Pf Prepos
Mode1 GG
No
Unit
Maintain=0 Release=1
PF Setpoints
75
UINT32
R/W
Gen PfP repos
Mode2 GG
No
Unit
Maintain=0 Release=1
PF Setpoints
75
UINT32
R/W
Gen PfP repos
Mode3 GG
No
Unit
Maintain=0 Release=1
PF Setpoints
76
Float
R/W
Gen Pf Traverse Rate GG
Sec
10 - 200
PF Setpoints
76
Float
R/W
Gen Pf Setpoint GG
PF
0.5 – -0.5
PF Setpoints
76
Float
R/W
Gen Pf Min Setpoint
Limit GG
PF
0.5 – 1
PF Setpoints
76
Float
R/W
Gen Pf Max Setpoint
Limit GG
PF
-1 - -0.5
PF Setpoints
76
Float
R/W
Gen Pf Preposition1 GG
PF
0.5 – -0.5
PF Setpoints
76
Float
R/W
Gen PfPreposition2 GG
PF
0.5 – -0.5
PF Setpoints
76
Float
R/W
Gen Pf Preposition3 GG
PF
0.5 – -0.5
Aux Input Settings
77
UINT32
R/W
Decs Aux Input
Mode GG
No
Unit
Voltage=0 Current=1
Page view 276