260 9440500990 Rev D
PROFIBUS Communication DECS-250N
Instance Name
Inst. #
Type
RW
Key Name
Unit
Range
System Param
66
Float
R/W
Rated Field Curr
Full Load GG
Amp
0.1 - 15
System Param
66
Float
R/W
Rated Field Curr
No Load GG
Amp
0.1 - 15
System Param
66
Float
R/W
Exciter Pole Ratio GG
No
Unit
1 - 10
AVR Setpoints
67
UINT32
R/W
Gen Vol Prepos
Mode1 GG
No
Unit
Maintain=0 Release=1
AVR Setpoints
67
UINT32
R/W
Gen Vol Prepos
Mode2 GG
No
Unit
Maintain=0 Release=1
AVR Setpoints
67
UINT32
R/W
Gen Vol Prepos
Mode3 GG
No
Unit
Maintain=0 Release=1
AVR Setpoints
68
Float
R/W
Gen Vol
Traverse Rate GG
Sec
10 - 200
AVR Setpoints
68
Float
R/W
Gen Vol Setpoint GG
V
84 - 144
AVR Setpoints
68
Float
R/W
Gen Vol Min Setpoint
Limit GG
%
70 - 120
AVR Setpoints
68
Float
R/W
Gen Vol Max Setpoint
Limit GG
%
70 - 120
AVR Setpoints
68
Float
R/W
Gen Vol
Preposition1 GG
V
84 - 144
AVR Setpoints
68
Float
R/W
Gen Vol
Preposition2 GG
V
84 - 144
AVR Setpoints
68
Float
R/W
Gen Vol
Preposition3 GG
V
84 - 144
FCR Setpoints
69
UINT32
R/W
Exc Cur Prepos
Mode1 GG
No
Unit
Maintain=0 Release=1
FCR Setpoints
69
UINT32
R/W
Exc Cur Prepos
Mode2 GG
No
Unit
Maintain=0 Release=1
FCR Setpoints
69
UINT32
R/W
Exc Cur Prepos
Mode3 GG
No
Unit
Maintain=0 Release=1
FCR Setpoints
70
Float
R/W
Exc Cur
Traverse Rate GG
Sec
10 - 200
FCR Setpoints
70
Float
R/W
Exc Cur Setpoint GG
Amp
0 - 12
FCR Setpoints
70
Float
R/W
Exc Cur Min Setpoint
Limit GG
%
0 - 120
FCR Setpoints
70
Float
R/W
Exc Cur Max Setpoint
Limit GG
%
0 - 120
FCR Setpoints
70
Float
R/W
Exc Cur
Preposition1 GG
Amp
0 - 12
FCR Setpoints
70
Float
R/W
Exc Cur
Preposition2 GG
Amp
0 - 12
FCR Setpoints
70
Float
R/W
Exc Cur
Preposition3 GG
Amp
0 - 12
FVR Setpoints
71
UINT32
R/W
Exc Vol Prepos
Mode1 GG
No
Unit
Maintain=0 Release=1
FVR Setpoints
71
UINT32
R/W
Exc Vol Prepos
Mode2 GG
No
Unit
Maintain=0 Release=1
FVR Setpoints
71
UINT32
R/W
Exc Vol Prepos
Mode3 GG
No
Unit
Maintain=0 Release=1
FVR Setpoints
72
Float
R/W
Exc Vol Traverse Rate GG
Sec
10 - 200