  • TROUBLESHOOTING
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 240
9440500990 Rev D 225
DECS-250N Modbus™ Communication
Name
Register
Type
Bytes
R/W
Unit
Range
UEL Secondary Curve Y5
41828
Float
4
R W
kilovar
0 1.5 • Rated kVA
SCL Primary Reference Hi
41830
Float
4
R W
Amp
0 - 66000
SCL Primary Reference Lo
41832
Float
4
R W
Amp
0 - 66000
SCL Primary Time Hi
41834
Float
4
R W
Second
0 - 60
SCL Primary No Response Time
41836
Float
4
R W
Second
0 - 10
SCL Secondary Reference Hi
41838
Float
4
R W
Amp
0 - 66000
SCL Secondary Reference Lo
41840
Float
4
R W
Amp
0 - 66000
SCL Secondary Time Hi
41842
Float
4
R W
Second
0 - 60
SCL Secondary No Response Time
41844
Float
4
R W
Second
0 - 10
SCL Scale Enable
41846
Uint32
4
R W
n/a
Disabled=0
Auxiliary Input=1
AEM RTD 1=2
AEM RTD 2=3
AEM RTD 3=4
AEM RTD 4=5
AEM RTD 5=6
AEM RTD 6=7
AEM RTD 7=8
AEM RTD 8=9
SCL Scale Signal 1
41848
Float
4
R W
Limiter
Scale
Volt
or Deg F
Adjustment range is determined by register
41846.
-10 10 V when 41846 = 1
-58 482°F when 41846 = 2-8
SCL Scale Signal 2
41850
Float
4
R W
Limiter
Scale
Volt
or Deg F
Adjustment range is determined by register
41846.
-10 10 V when 41846 = 1
-58 482°F when 41846 = 2-8
SCL Scale Signal 3
41852
Float
4
R W
Limiter
Scale
Volt
or Deg F
Adjustment range is determined by register
41846.
-10 10 V when 41846 = 1
-58 482°F when 41846 = 2-8
SCL Scale Point 1
41854
Float
4
R W
Percent
0 - 200
SCL Scale Point 2
41856
Float
4
R W
Percent
0 - 200
SCL Scale Point 3
41858
Float
4
R W
Percent
0 - 200
Var Limit Enable
41860
Uint32
4
R W
n/a
Disabled=0 Enabled=1
Var Limit Primary Delay
41862
Float
4
R W
Second
0 - 300
Var Limit Primary Setpoint
41864
Float
4
R W
Percent
0 - 200
Var Limit Secondary Delay
41866
Float
4
R W
Second
0 - 300
Var Limit Secondary Setpoint
41868
Float
4
R W
Percent
0 - 200
Var Limit Enable Status
41870
Uint32
4
R
n/a
Off=0 On=1
OEL Primary Takeover Reset Time
Coefficient Off
41872
Float
4
R W
n/a
0.01 100
OEL Primary Takeover Reset Time
Coefficient On
41874
Float
4
R W
n/a
0.01 100
OEL Secondary Takeover Reset Time
Coefficient Off
41876
Float
4
R W
n/a
0.01 100
OEL Secondary Takeover Reset Time
Coefficient On
41878
Float
4
R W
n/a
0.01 100
OEL Primary Takeover Reset Type Off
41880
Uint32
4
R W
n/a
Inverse=0,Integrating=1,Instantaneous=2
OEL Primary Takeover Reset Type On
41882
Uint32
4
R W
n/a
Inverse=0,Integrating=1,Instantaneous=2
OEL Secondary Takeover Reset Type Off
41884
Uint32
4
R W
n/a
Inverse=0,Integrating=1,Instantaneous=2
OEL Secondary Takeover Reset Type On
41886
Uint32
4
R W
n/a
Inverse=0,Integrating=1,Instantaneous=2
Setpoints
Table 29. Setpoint Group Parameters
Name
Register
Type
Bytes
R/W
Unit
Range
Field Current Regulation Setpoint
42200
Float
4
R W
Amp
Setpoint adjustment range determined
by registers 42212 and 42214.
Field Current Regulation Traverse Rate
42202
Float
4
R W
Second
10 200
Page view 240