Basler-electric DECS-250N User Manual Page 17

  • Download
  • Add to my manuals
  • Print
  • Page
    / 370
  • Table of contents
  • TROUBLESHOOTING
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 16
9440500990 Rev C 1
DECS-250N Introduction
Introduction
DECS-250N Digital Excitation Control Systems offer precise excitation control and machine protection in
a compact package. DECS-250N adaptability to many applications is assured through configurable
contact inputs and outputs, flexible communication capabilities, and programmable logic implemented
with the provided BESTCOMSPlus
®
software.
Features and Functions
DECS-250N features and functions include:
Precise excitation control for synchronous generator or synchronous motor applications
o Power factor and var metering values will be opposite in motor mode
Five excitation control modes:
o Automatic Voltage Regulation (AVR)
o Field Current Regulation (FCR)
o Field Voltage Regulation (FVR)
o Power Factor Regulation (PF)
o Var Regulation (var)
Three pre-position setpoints for each excitation control mode
Internal tracking between operating mode setpoints and external tracking of a second DECS
excitation setpoint
Two PID stability groups with Auto Tune feature
Remote setpoint control input accepts analog voltage or current control signal
Real-time metering
Optional automatic synchronizer
Optional integrated power system stabilizer (PSS)
o Generator or motor control modes, accommodates phase rotation changes between
modes
o Speed and power sensing or speed-only sensing
o Two wattmeter or three-wattmeter methods of power measurement
Soft start and voltage buildup control
Five limiting functions:
o Overexcitation: summing point and takeover
o Underexcitation
o Stator current
o Reactive power (var)
o Underfrequency
Twenty protection functions:
o Generator undervoltage (27)
o Generator overvoltage (59)
o Loss of sensing (LOS)
o Overfrequency (81O)
o Underfrequency (81U)
o Reverse power (32R)
o Loss of excitation (40Q)
o Field overvoltage
o Field overcurrent
o Loss of PMG
o Exciter diode failure
o Sync-check (25)
o Eight configurable protection elements
IRIG or network time synchronization
Sixteen contact sensing inputs
o Two fixed-function inputs: Start and Stop
o Fourteen programmable inputs