312 9440500990 Rev D
Specifications DECS-250N
Steady-State Stability ....................... ±0.25% at rated PF with constant generator frequency and ambient
temperature
Temperature Drift ............................. ±0.5% between 0 and 40°C at constant load and generator
frequency
Var Operating Mode
Setpoint Range ................................ 100% (leading) to +100% (lagging) of the generator nominal
apparent power in increments of 0.1%
Regulation Accuracy ........................ ±2.0% of the nominal generator apparent power rating at the rated
generator frequency
Power Factor Operating Mode
Setpoint Range ................................ 0.5 to 1.0 (lagging) and 0.5 to -1.0 (leading), in increments of 0.005
Regulation Accuracy ........................ ±0.02 PF of the PF setpoint for the real power between 10 and 100%
at the rated frequency
Parallel Compensation
Modes ............................................... Reactive Droop, Line Drop, and Reactive Differential (Cross-Current)
Cross-Current Input Burden ............. Can exceed 1 VA if external resistors are added to the CT circuit for
cross-current compensation
Cross-Current Input Terminals ......... CCCT+, CCCT
Setpoint Range
Reactive Droop ................................ 0 to +30% of Rated Voltage
Line Drop .......................................... 0 to 30% of Rated Voltage
Cross-Current ................................... 30 to +30% of Primary CT Current
Generator Protection Functions
Overvoltage (59) and Undervoltage (27)
Pickup
Range ............................................... 1 to 600,000 Vac
Increment ......................................... 1 Vac
Time Delay
Range ............................................... 0.1 to 60 s
Increment ......................................... 0.1 s
Loss of Sensing
Time Delay
Range ............................................... 0 to 30 s
Increment ......................................... 0.1 s
Voltage Balanced Level
Range ............................................... 0 to 100% of Positive Sequence Voltage
Increment ......................................... 0.1%
Voltage Unbalanced Level
Range ............................................... 0 to 100% of Positive Sequence Voltage
Increment ......................................... 0.1%