9440500990 Rev D 45
DECS-250N Protection
A
Voltage Balanced Level: Adjustable from 0 to 100% in 0.1% increments.
B
Voltage Unbalanced Level: Adjustable from 0 to 100% in 0.1% increments.
C
Time Delay: Adjustable from 0 to 30 seconds in 0.1 second increments.
D
Transfer to Manual: Select Disabled or Enabled.
E
Mode: Select Disabled or Enabled.
Frequency Protection
BESTCOMSPlus Navigation Path: Settings Explorer, Protection, Frequency
HMI Navigation Path: Settings, Protection, Frequency Protection 81
The frequency of the generator terminal voltage is monitored for overfrequency and under-frequency
conditions.
Overfrequency
An overfrequency condition occurs when the frequency of the generator voltage exceeds the 81O pickup
threshold
A
for the duration of the 81O time delay setting
B
. Overfrequency protection can be enabled and
disabled
C
without altering the pickup and time delay settings. Overfrequency pickup and trip elements in
BESTlogicPlus can be used in a logic scheme to initiate corrective action in response to the condition.
BESTCOMSPlus overfrequency settings are illustrated in Figure 31.
Figure 31. Overfrequency Protection Settings
A
Overfrequency (81O) Pickup (Hz): Adjustable from 30 to 70 hertz in 0.01 hertz increments.
B
Overfrequency (81O) Time Delay (s): Adjustable from 0.1 to 300 seconds in 0.1 second increments.
C
Overfrequency (81O) Mode: Select Disabled or Over.
Underfrequency
An underfrequency condition occurs when the frequency of the generator voltage decreases below the
81U pickup threshold
A
for the duration of the 81U time delay setting
B
. A voltage inhibit setting
C
, expressed
as a percentage of the rated generator voltage, can be implemented to prevent an underfrequency trip
from occurring during startup when the generator voltage is rising toward the nominal level.
Underfrequency protection can be enabled and disabled
D
without altering the pickup, delay, and inhibit
settings. Underfrequency pickup and trip elements in BESTlogicPlus can be used in a logic scheme to
initiate corrective action in response to the condition. BESTCOMSPlus underfrequency settings are
illustrated in Figure 32.