DECS-250N Event Recorder
Mode Triggers
Mode triggers initiate data logging as a result of an internal or external DECS-250N status change. A data
log can be triggered by any of the following status changes:
Start or Stop mode selected
A
Soft Start mode enabled or disabled
B
Underfrequency condition
C
Manual or AVR mode selected
D
Power Factor or Var mode selected
E
Limiter active
F
Voltage matching enabled or disabled
G
Primary or secondary DECS selected
H
PSS enabled or disabled
I
Auto Sync enabled or disabled
J
FCR or FVR mode selected
K
Droop mode enabled or disabled
L
Network Load Share enabled or disabled
M
Line drop compensation enabled or disabled
N
Cross-current compensation enabled or disabled
O
Test mode enabled or disabled
P
Mode trigger settings are illustrated in Figure 81.
Figure 81. Data Log Mode Triggers
A
Start/Stop: Select Trigger on stop mode, Trigger on start mode, or No Trigger.
B
Soft Start: Select Soft Start Mode Off, Soft Start Mode Active, or No Trigger.
C
Underfrequency: Select Inactive Trigger, Active Trigger, or No Trigger.
D
Auto/Manual: Select Manual Control Trigger, AVR Control Trigger, or No Trigger.
E
Var/Power Factor: Select Operating Mode Off Trigger, Operating Mode PF Trigger, Operating Mode
VAR Trigger, or No Trigger.
F
Limiters: Select Limiter Off Trigger, Limiter UEL Trigger, Limiter OEL Trigger, Limiter UEL OEL Trigger,
Limiter SCL Trigger, Limiter UEL SCL Trigger, Limiter OEL SCL Trigger, Limiter UEL OEL SCL Trigger, or
No Trigger.
G
Voltage Matching: Select VMM Off Trigger, VMM On Trigger, or No Trigger.
H
Pri/Sec DECS: Select Primary Trigger, Secondary Trigger, or No Trigger.
I
PSS: Select Disabled Trigger, Enabled Trigger, or No Trigger.
J
Auto Sync: Select Disabled Trigger, Enabled Trigger, or No Trigger.
K
FCR/FVR: Select FVR Trigger, FCR Trigger, or No Trigger.
L
Droop: Select Disabled Trigger, Enabled Trigger, or No Trigger.
M
Network Load Share: Disabled Trigger, Enabled Trigger, or No Trigger.
N
Line Drop Comp.: Select Disabled Trigger, Enabled Trigger, or No Trigger.
O
Cross-Current Comp.: Select Disabled Trigger, Enabled Trigger, or No Trigger.
P
Test: Select Disabled Trigger, Enabled Trigger, or No Trigger.