DECS-250N Metering
the FVR indicator changes from gray to green. FCR mode is selected by clicking the FCR button. FVR
mode is selected by clicking the FVR button.
Var/PF Mode: Three indicators report whether Var mode is active, Power Factor mode is active, or
neither mode is active. When Var mode is active the var indicator changes from gray to green. When
Power Factor mode is active, the PF indicator changes from gray to green. When neither mode is active,
the Off indicator changes from gray to green. Var mode is enabled by clicking the var button. Power
Factor mode is enabled by clicking the PF button. Neither mode is enabled by clicking the Off button.
Only one mode can be enabled at any time.
Setpoint Pre-position: A control button and indicator is provided for the three setpoint pre-positions.
Clicking the Set 1 button adjusts the excitation setpoint to the Pre-position 1 value and changes the Pre-
position 1 indicator to green. Pre-positions 2 and 3 are selected by clicking either the Set 2 or Set 3
button.
Setpoints: Five status fields display the active setpoints for AVR mode, FCR mode, FVR mode, var
mode, and Power Factor mode. These active setpoints, represented by a yellow font, are not to be
confused with metered analog values which are represented by a green font throughout BESTCOMSPlus.
For details on operating setpoint settings, see the Regulation chapter.
Setpoint Fine Adjust: Clicking the Raise button increases the active operating setpoint. Clicking the
Lower button decreases the active operating setpoint. The raise and lower increment is a function of the
setpoint range of adjustment and the active mode traverse rate. The increments are directly proportional
to the adjustment range and inversely proportional to the traverse rate.
Alarm Status: The Alarm Status indicator changes from gray to green when there is an active alarm.
PSS Status: The PSS Status indicator changes from gray to green when the PSS is active.
Null Balance: The Null Balance indicator changes from gray to green when the setpoint of the inactive
operating modes (AVR, FCR, FVR, var, and PF) match the setpoint of the active mode.
Virtual Switches: These buttons control the open or closed status of the six virtual switches. Clicking the
Open button sets the switch to the open position and changes the switch indicator to gray. Clicking the
Close button sets the switch to the closed position and changes the switch indicator to red. A dialog will
appear asking if you are sure you want to open or close the switch.
Metering Summary
BESTCOMSPlus Navigation Path: Metering Explorer, Summary
HMI Navigation Path: Not available via HMI
All of the metering values displayed on the individual, previously-described metering screens are
consolidated on the metering summary screen. Primary- and per-unit values are available. Figure 68
illustrates the primary-values metering summary screen. The primary- and per-unit metering summary
screens are available only in BESTCOMSPlus.