DECS-250N Modbus™ Communication
Group
Name
Register
Type
Bytes
R/W
Unit
Range
System
Configuration
DECS Auxiliary Summing Mode
42602
Uint32
4
R W
n/a
Voltage=0 Var=1
System
Configuration
DECS Auxiliary Input Mode
42604
Uint32
4
R W
n/a
Voltage=0 Current=1
System
Configuration
DECS Auxiliary Input Function
42606
Uint32
4
R W
n/a
DECS Input=0
PSS Test Input=1
Limiter Selection=2
System
Configuration
DECS Auxiliary Voltage Gain
42608
Float
4
R W
n/a
-99 99
System
Configuration
DECS Auto Track Time Delay
42610
Float
4
R W
Second
0 - 8
System
Configuration
DECS Auto Track Traverse Rate
42612
Float
4
R W
Second
1 - 80
System
Configuration
DECS Null Balance Level
42614
Float
4
R W
Percent
0 - 9999
System
Configuration
DECS Auto Trans Time Delay
42616
Float
4
R W
Second
0 - 8
System
Configuration
DECS Auto Trans Traverse Rate
42618
Float
4
R W
Second
1 - 80
Gen Volt
Configuration
Ratio Primary
42620
Float
4
R W
n/a
1 - 500000
Gen Volt
Configuration
Ratio Secondary
42622
Float
4
R W
n/a
1 - 600
Gen Volt
Configuration
Rated Primary LL
42624
Float
4
R W
Volt
1 - 500000
Bus Volt
Configuration
Ratio Primary
42626
Float
4
R W
n/a
1 - 500000
Bus Volt
Configuration
Ratio Secondary
42628
Float
4
R W
n/a
1 - 600
Bus Volt
Configuration
Rated Primary LL
42630
Float
4
R W
Volt
1 - 500000
Gen Current
Configuration
Ratio Primary
42632
Float
4
R W
n/a
1 - 99999
Gen Current
Configuration
Ratio Secondary
42634
Int32
4
R W
n/a
1=1 5=5
Gen Current
Configuration
Rated Primary
42636
Float
4
R
Amp
0 - 180000
DECS Control
Start Stop Request
42638
Uint32
4
R W
n/a
Stop=0 =1 Start =2
DECS Control
System Option Underfrequency Hz
42640
Float
4
R W
Hertz
40 - 75
DECS Control
System Input COM Port Manual Enabled
42642
Uint32
4
R W
n/a
Manual=1 Automatic=2
DECS Control
System Input COM Port PF var Enabled
42644
Uint32
4
R W
n/a
Off=0 PF=1 Var=2
DECS Control
System Input COM Port External Tracking
Enabled
42646
Uint32
4
R W
n/a
Disabled=0 Enabled=1
DECS Control
System Input COM Port Pre-position
Enabled
42648
Uint32
4
R W
n/a
NOT SET=0 SET=1
DECS Control
System Input COM Port Pre-position
Enabled 2
42650
Uint32
4
R W
n/a
NOT SET=0 SET=1
DECS Control
System Input COM Port Raise Enabled
42652
Uint32
4
R W
n/a
NOT SET=0 Raise=1
DECS Control
System Input COM Port Lower Enabled
42654
Uint32
4
R W
n/a
NOT SET=0 Lower=1
DECS Control
System Option Input Voltage Match
Enabled
42656
Uint32
4
R W
n/a
Disabled=0 Enabled=1
DECS Control
System Option Underfrequency Mode
42658
Uint32
4
R W
n/a
UF Limiter=0
V/Hz Limiter=1
DECS Control
System Option Limiter Mode
42660
Uint32
4
R W
n/a
Off=0 UEL=1 OEL=2 UEL &
OEL=3 SCL=4 UEL &
SCL=5 OEL & SCL=6 UEL
& OEL & SCL=7
DECS Control
System Option Voltage Match Band
42662
Float
4
R W
Percent
0 - 20
DECS Control
System Option Voltage Match Reference
42664
Float
4
R W
Percent
0 - 700
DECS Control
System Option Underfrequency Slope
42666
Float
4
R W
n/a
0 - 3
DECS Control
Startup Primary Soft-start Bias
42668
Float
4
R W
Percent
0 - 90