DECS-250N BESTlogicPlus
Name Description Symbol
LOAD SHARE
DISABLE
This element allows load sharing with specific
units on the network to be disabled.
When an input to this block is true, load share
data received from that unit is ignored by the
DECS-250N.
LOSS OF SENSING
DISABLE
When true, this element disables the Loss of
Sensing function.
LOSS OF SENSING
TRANSFER
DISABLE
When true, this element disables the transfer
to Manual mode during a Loss of Sensing
condition.
LOWER ENABLE When true, this element lowers the active
setpoint.
MANUAL ENABLE When true, this element switches the unit to
Manual mode.
MANUAL MODE
FCR ONLY
When true, this element switches the Manual
mode to FCR.
NETWORK LOAD
SHARE DISABLE
When true, this element disables network load
sharing.
NLS BROADCAST This element functions in conjunction with the
Network Load Share Status inputs on all units
on the network. When an input is true, the
corresponding Network Load Share Status
input on all units on the network is true.