DECS-250N Event Recorder
Event Recorder
DECS-250N event recorder functions include sequence-of-events recording (SER), data logging
(oscillography), and trending.
Sequence-of-Events Recording
BESTCOMSPlus Navigation Path: Metering Explorer, Reports, Sequence of Events
HMI Navigation Path: Metering Explorer, Reports, Sequence of Events
A sequence of events recorder monitors the internal and external status of the DECS-250N. Events are
scanned at four millisecond intervals with 1,023 events stored per record. All changes of state that occur
during each scan are time- and date-stamped. Sequence of events reports are available through
BESTCOMSPlus
®
.
Any one of over 400 monitored data/status points can be recorded in the sequence of events. All points
are enabled by default. Sequence of Events Setup is illustrated in Figure 79.
Figure 79. Sequence of Events Setup
Data Logging
BESTCOMSPlus Navigation Path: Settings Explorer, Report Configuration, DataLog
HMI Navigation Path: Settings, Configuration Settings, Data Log
The data logging function of the DECS-250N can record up to 6 oscillography records. DECS-250N
oscillography records use the IEEE Standard Common Format for Transient Data Exchange
(COMTRADE). Each record is time- and date-stamped. After 6 records have been recorded, the DECS-
250N begins recording the next record over the oldest record. Because oscillography records are stored
in nonvolatile memory, interruptions in DECS-250N control power will not affect the integrity of the
records. Data log settings are configured in BESTCOMSPlus and illustrated in Figure 80 through Figure