238 9440500990 Rev D
Modbus™ Communication DECS-250N
Name Register Type
Byte
s
R/W Unit Range
AVR Maximum Setpoint
47709
Float
4
R
n/a
Setpoint adjustment range
determined by registers 47665
and 47525.
Var Maximum Setpoint
47711
Float
4
R
n/a
Setpoint adjustment range
determined by registers 47667
and Rated VA.
PF Maximum Setpoint
47713
Float
4
R
n/a
Range determined by register
47669.
Reserved 11
47715-
740
C6 Filler
52
n/a
n/a
n/a
Soft Start Threshold
47741
Float
4
R W
Percent
0 - 90
Soft Start Duration
47743
Float
4
R W
Second
1 - 7200
Underfrequency Corner Frequency
47745
Float
4
R W
Hertz
40 - 75
Slope of Underfrequency Curve
47747
Float
4
R W
n/a
0 - 3
Width of Voltage Matching Window
47749
Float
4
R W
Percent
0 - 20
Voltage Matching Reference
47751
Float
4
R W
Percent
0 - 700
Fine Voltage Adjust Band
47753
Float
4
R W
Percent
0 - 30
Time Required for Loss of Sensing
47755
Float
4
R W
Second
0 - 30
Loss of Sensing Level Under Balanced
Conditions
47757
Float
4
R W
Percent
0 - 100
Loss of Sensing Level Under Unbalanced
Conditions
47759
Float
4
R W
Percent
0 - 100
Reserved 12
47761-
800
C7 Filler
80
n/a
n/a
n/a
On-line High OEL Level
47801
Float
4
R W
Amp
0 - 30
Time Allowed for On-line High OEL Level
47803
Float
4
R W
Second
0 - 10
On-line Medium OEL Level
47805
Float
4
R W
Amp
0 - 20
Time Allowed for On-line Medium OEL Level
47807
Float
4
R W
Second
0 - 120
On-line Low OEL Level
47809
Float
4
R W
Amp
0 - 15
Reserved 13
47811
Float
4
R W
var
0 - 99
Time Allowed for Off-line High OEL
47813
Float
4
R W
Second
0 - 10
Off-line High OEL Level
47815
Float
4
R W
Amp
0 - 30
Off-line Low OEL Level
47817
Float
4
R W
Amp
0 - 15
First UEL Point kW Value
47819
Float
4
R W
kilowatt
0 1.5 • Rated kVA
Second UEL Point kW Value
47821
Float
4
R W
kilowatt
0 1.5 • Rated kVA
Third UEL Point kW Value
47823
Float
4
R W
kilowatt
0 1.5 • Rated kVA
Fourth UEL Point kW Value
47825
Float
4
R W
kilowatt
0 1.5 • Rated kVA
Fifth UEL Point kW Value
47827
Float
4
R W
kilowatt
0 1.5 • Rated kVA
First UEL Point kvar Value
47829
Float
4
R W
kilovar
0 1.5 • Rated kVA
Second UEL Point kvar Value
47831
Float
4
R W
kilovar
0 1.5 • Rated kVA
Third UEL Point kvar Value
47833
Float
4
R W
kilovar
0 1.5 • Rated kVA
Fourth UEL Point kvar Value
47835
Float
4
R W
kilovar
0 1.5 • Rated kVA
Fifth UEL Point kvar Value
47837
Float
4
R W
kilovar
0 1.5 • Rated kVA
SCL High Limit Level
47839
Float
4
R W
Amp
0 - 66000
Time Allowed at SCL High Limit Level
47841
Float
4
R W
Second
0 - 60
SCL Low Limit Level
47843
Float
4
R W
Amp
0 - 66000
Takeover OEL Offline High Limit Level
47845
Float
4
R W
Amp
0 - 30
Takeover OEL Offline Low Limit Level
47847
Float
4
R W
Amp
0 - 15
Takeover OEL Offline Time Dial
47849
Float
4
R W
n/a
0.1 - 20
Takeover OEL Online High Limit Level
47851
Float
4
R W
Amp
0 - 30
Takeover OEL Online Low Limit Level
47853
Float
4
R W
Amp
0 - 15
Takeover OEL Online Time Dial
47855
Float
4
R W
n/a
0.1 - 20
Reserved 14
47857-
860
C8 Filler
8
n/a
n/a
n/a