172 9440500990 Rev D
Configuration DECS-250N
A
Generator Voltage Rating: Adjustable from 1 to 500,000 Vac in 1 Vac increments.
B
Generator Frequency Rating: Select 50 or 60 Hz.
C
Generator PF (Power Factor): Adjustable from 0.5 to 0.5 in 0.001 increments.
D
Generator Voltamperes: Adjustable from 0 to 1,000,000 kVA in 0.01 kVA increments.
E
Generator Current: Read-only value calculated from the generator VA and voltage.
F
Generator Power: Read-only value calculated from the generator voltage, current, and PF.
G
Generator Reactive Power: Read-only value calculated from the generator VA and PF.
H
Field Voltage No Load: Adjustable from 1 to 264 Vdc in 0.1 Vdc increments.
I
Field Current No Load: Adjustable from 0.1 to 20 Adc in 0.1 Adc increments.
J
Field Voltage Full Load: Adjustable from 1 to 264 Vdc in 0.1 Vdc increments.
K
Field Current Full Load: Adjustable from 0.1 to 20 Adc in 0.1 Adc increments.
L
Pole Ratio: Adjustable from 0 to 10 in 0.01 increments.
M
Calculator: Choose number of exciter and generator poles to calculate pole ratio.
N
Bus Voltage: Adjustable from 1 to 500,000 Vac in 1 Vac increments.
O
Power Input Voltage: Adjustable from 1 to 480 V in .01 increments.
P
Inverted Output: Check box to enable inversion, uncheck to disable inversion.
Sensing Transformer Ratings and Configuration
BESTCOMSPlus Navigation Path: Settings Explorer, System Parameters, Sensing Transformers
HMI Navigation Path: Settings, System Parameters, Sensing Transformers
DECS-250N configuration includes entry of the primary and secondary values for the transformers that
supply generator and bus sensing values to the DECS-250N. These configuration settings are illustrated
in Figure 150.
Generator PT
Voltage settings for the generator PT primary
A
and secondary
B
windings establish the nominal PT
voltages expected by the DECS-250N. ABC or ACB phase rotation
C
can be accommodated. Options for
the generator voltage sensing connections
D
include single-phase (across phases C and A) and three-
phase sensing using three-wire connections.
Generator CTs
Current settings for the generator CT primary
E
and secondary
F
windings establish the nominal CT current
values expected by the DECS-250N. DECS-250N sensing current can be obtained from a single phase or
all three generator phases
G
.
Bus PT
Voltage settings for the bus PT primary
H
and secondary
I
windings establish the nominal bus PT voltages
expected by the DECS-250N. Options for the bus voltage sensing connections
J
include single-phase
(across phases A and C) and three-phase sensing using three-wire delta connections.