Basler-electric BE1-700 Modbus Protocol User Manual

Browse online or download User Manual for Relay Basler-electric BE1-700 Modbus Protocol. Basler Electric BE1-700 Modbus Protocol User Manual

  • Download
  • Add to my manuals
  • Print

Summary of Contents

Page 1 - INSTRUCTION MANUAL

INSTRUCTION MANUAL FOR DIGITAL PROTECTIVE RELAY BE1-700 MODBUS™ PROTOCOL Publication: 9376700991 Revision: D 01/12

Page 2

ii BE1-700 Modbus™ Protocol 9376700991 Rev D

Page 3 - INTRODUCTION

9376700991 Rev D BE1-700 Modbus™ Protocol 1-1 SECTION 1 • GENERAL INFORMATION Introduction This document describes the Modbus™ communications protoc

Page 4 - HIGHLAND IL 62249 USA

1-2 BE1-700 Modbus™ Protocol 9376700991 Rev D response will substitute an exception response code for the data block. The length of this field varie

Page 5 - REVISION HISTORY

9376700991 Rev D BE1-700 Modbus™ Protocol 1-3 Table 1-1. Timing Considerations Baud Rate 3.5 Character Time (ms) Message Tx Time(s) 128 Bytes 256 B

Page 6

1-4 BE1-700 Modbus™ Protocol 9376700991 Rev D Figure 1-1. Basler Modbus/TCP Device Discovery Screen Obtain the factory test report which is includ

Page 7 - CONTENTS

9376700991 Rev D BE1-700 Modbus™ Protocol 1-5 Figure 1-3. DOS Configuration Utility Screen - Password Type 3 (Enable DHCP Client) and press the En

Page 8

1-6 BE1-700 Modbus™ Protocol 9376700991 Rev D Figure 1-5. DOS Configuration Utility Screen – Don’t Enable DHCP Client Type 1 and press the Enter k

Page 9 - TABLE OF CONTENTS

9376700991 Rev D BE1-700 Modbus™ Protocol 1-7 Type 3 and press the Enter key. See Figure 1-8. Then type the Default Gateway address for the BE1-700

Page 10

1-8 BE1-700 Modbus™ Protocol 9376700991 Rev D Start the Basler Modbus/TCP Device Discovery application that can be found on the CD provided with the

Page 11 - Introduction

9376700991 Rev D BE1-700 Modbus™ Protocol 1-9 4) Testing your network can be done from your computer’s DOS command shell. To open a DOS command sh

Page 13 - Running

1-10 BE1-700 Modbus™ Protocol 9376700991 Rev D Figure 1-14. DOS Command Example of Default IP Address Detected 7) Once your PC has an IP address,

Page 14

9376700991 Rev D BE1-700 Modbus™ Protocol 1-11 The response message contains the data queried. The data block contains the block length in bytes fol

Page 15

1-12 BE1-700 Modbus™ Protocol 9376700991 Rev D Subfunction Hi = 00 (hex) Subfunction Lo = 04 (hex) Data Hi = xx (don't care) Data Lo = x

Page 16

9376700991 Rev D BE1-700 Modbus™ Protocol 1-13 Preset Single Register (Write Single Holding Register) A Preset Single Register query message request

Page 17

1-14 BE1-700 Modbus™ Protocol 9376700991 Rev D The same byte alignments are required to write. Long Integer Data Format (LI) The Modbus long integer

Page 18

9376700991 Rev D BE1-700 Modbus™ Protocol 1-15 Holding Register K (Hi Byte) 'P' Value K (Lo Byte) 'A' K+1 (Hi Byte) '

Page 19

1-16 BE1-700 Modbus™ Protocol 9376700991 Rev D example, a user cannot make changes from COM0 at the same time a remote user is making changes via Mo

Page 20 - Read Holding Registers

9376700991 Rev D BE1-700 Modbus™ Protocol 1-17 Report Generation Registers The BE1-700 generates numerous ASCII reports available via serial command

Page 21 - Listen Only Mode

1-18 BE1-700 Modbus™ Protocol 9376700991 Rev D

Page 22 - Preset Multiple Registers

9376700991 Rev D BE1-700 Modbus™ Protocol 2-1 SECTION 2 • REGISTER TABLE Mapping BE1-700 Parameters into Modicon Holding Register Address Space Gene

Page 23 - Data Formats

9376700991 Rev D BE1-700 Modbus™ Protocol i INTRODUCTION This instruction manual provides detailed information about the BE1-700 Digital Protective

Page 24 - Integer Data Format (INT)

Holding Read/Write Data Register Parameter Supported Format Notes 2-2 BE1-700 Modbus™ Protocol 9376700991 Rev D 40001 Exit R

Page 25 - Session Access Registers

Holding Read/Write Data Register Parameter Supported Format Notes 9376700991 Rev D BE1-700 Modbus™ Protocol 2-3 The following i

Page 26 - Fault Summary Registers

Holding Read/Write Data Register Parameter Supported Format Notes 2-4 BE1-700 Modbus™ Protocol 9376700991 Rev D 40406-07 79 Fi

Page 27 - Report Generation Registers

Holding Read/Write Data Register Parameter Supported Format Notes 9376700991 Rev D BE1-700 Modbus™ Protocol 2-5 40498-99 27P P

Page 28

Holding Read/Write Data Register Parameter Supported Format Notes 2-6 BE1-700 Modbus™ Protocol 9376700991 Rev D 40872 Setting

Page 29 - SECTION 2 • REGISTER TABLE

Holding Read/Write Data Register Parameter Supported Format Notes 9376700991 Rev D BE1-700 Modbus™ Protocol 2-7 41102 Programm

Page 30 - Control Parameters

Holding Read/Write Data Register Parameter Supported Format Notes 2-8 BE1-700 Modbus™ Protocol 9376700991 Rev D 41355-60 Fault

Page 31 - Group Setting Parameters

Holding Read/Write Data Register Parameter Supported Format Notes 9376700991 Rev D BE1-700 Modbus™ Protocol 2-9 41708 Programm

Page 32

Holding Read/Write Data Register Parameter Supported Format Notes 2-10 BE1-700 Modbus™ Protocol 9376700991 Rev D 42079-84 Prog

Page 33 - Global Setting Parameters

Holding Read/Write Data Register Parameter Supported Format Notes 9376700991 Rev D BE1-700 Modbus™ Protocol 2-11 42434-39 Prog

Page 34

ii BE1-700 Modbus™ Protocol 9376700991 Rev D First Printing: June 2004 Printed in USA © 2004-2012 Basler Electric, Highland Illinois 62249 USA All R

Page 35

Holding Read/Write Data Register Parameter Supported Format Notes 2-12 BE1-700 Modbus™ Protocol 9376700991 Rev D 42800-05 Prog

Page 36

Holding Read/Write Data Register Parameter Supported Format Notes 9376700991 Rev D BE1-700 Modbus™ Protocol 2-13 43173 Program

Page 37

Holding Read/Write Data Register Parameter Supported Format Notes 2-14 BE1-700 Modbus™ Protocol 9376700991 Rev D 43511-15 Virt

Page 38

Holding Read/Write Data Register Parameter Supported Format Notes 9376700991 Rev D BE1-700 Modbus™ Protocol 2-15 43771-75 Virt

Page 39

Holding Read/Write Data Register Parameter Supported Format Notes 2-16 BE1-700 Modbus™ Protocol 9376700991 Rev D 47399-00 Brea

Page 40

Holding Read/Write Data Register Parameter Supported Format Notes 9376700991 Rev D BE1-700 Modbus™ Protocol 2-17 47475-76 Peak

Page 41

Holding Read/Write Data Register Parameter Supported Format Notes 2-18 BE1-700 Modbus™ Protocol 9376700991 Rev D 49726-27 Phas

Page 42

9376700991 Rev D BE1-700 Modbus™ Protocol i SECTION 3 • REGISTER DETAILS TABLE OF CONTENTS SECTION 3 • REGISTER DETAILS...

Page 43 - Report Parameters

ii BE1-700 Modbus™ Protocol 9376700991 Rev D

Page 44

9376700991 Rev D BE1-700 Modbus™ Protocol 3-1 SECTION 3 • REGISTER DETAILS Introduction This section details the register formats and data ranges of

Page 45 - Metering Parameters

9376700991 Rev D BE1-700 Modbus™ Protocol iii REVISION HISTORY The following information provides a historical summary of the changes made to this i

Page 46

3-2 BE1-700 Modbus™ Protocol 9376700991 Rev D 41809 Programmable 62 Timer Logic Mode INT 41842 Programmable 162 Timer Logic Mode INT

Page 47 - SECTION 3 • REGISTER DETAILS

9376700991 Rev D BE1-700 Modbus™ Protocol 3-3 42111 Programmable 43 Virtual Switch Logic Mode INT 42112 Programmable 143 Virtual Switch Logic

Page 48

3-4 BE1-700 Modbus™ Protocol 9376700991 Rev D Bit 9 - Virtual Output 9 status Bit 8 - Virtual Output 8 status Bit 7 - Virtual Output 7 status Bit 6

Page 49

9376700991 Rev D BE1-700 Modbus™ Protocol 3-5 Bit 1 - 159X tripped Bit 0 - 59X tripped Bit 0 - 159 phase tripped Logic Term Count Term Count Registe

Page 50

3-6 BE1-700 Modbus™ Protocol 9376700991 Rev D 40039 Report Selection SI Read: Returns the current value of Report Selection. Writing to Re

Page 51 - Logic Mask and Terms

9376700991 Rev D BE1-700 Modbus™ Protocol 3-7 Control Parameters All values read from and written to Select and Operate registers are ASCII characte

Page 52

3-8 BE1-700 Modbus™ Protocol 9376700991 Rev D 40135 Select 101 Virtual Breaker Control Switch ASC(1) Read: To read a value other than ASCII

Page 53 - Logic Term Count

9376700991 Rev D BE1-700 Modbus™ Protocol 3-9 Read: To read a value other than ASCII character 'X', the Select Output register must be t

Page 54

3-10 BE1-700 Modbus™ Protocol 9376700991 Rev D 40273 50TQ Directional Mode ASC(1) 40278 150TP Directional Mode ASC(1) 40283 150TN Direc

Page 55

9376700991 Rev D BE1-700 Modbus™ Protocol 3-11 40429-30 27R Pickup FP Read and Write: 30.0 to 250 40431 27R Control Mode ASC(1) Rea

Page 56

iv BE1-700 Modbus™ Protocol 9376700991 Rev D

Page 57

3-12 BE1-700 Modbus™ Protocol 9376700991 Rev D 40498-99 27P Pickup FP 40510-11 127P Pickup FP Read and Write: 10.0 to 300 40504-05 2

Page 58

9376700991 Rev D BE1-700 Modbus™ Protocol 3-13 Global Setting Parameters 40602-03 Power System Nominal Voltage FP Read and Write: 50 to 250

Page 59

3-14 BE1-700 Modbus™ Protocol 9376700991 Rev D 2 - 1200 Baud (Do not select for Port 2 Modbus communications) 3 - 2400 Baud 4 - 4800 Baud 5

Page 60

9376700991 Rev D BE1-700 Modbus™ Protocol 3-15 41039-40 VT Connection ASC(3) Read and Write: 3W for 3W 4W for 4W AB for AB BC for BC

Page 61

3-16 BE1-700 Modbus™ Protocol 9376700991 Rev D 41265-66 Major Alarm Mask MSBs BM(16) 41267-68 Minor Alarm Mask MSBs BM(16) 41269-70 Log

Page 62

9376700991 Rev D BE1-700 Modbus™ Protocol 3-17 41284 Output Hold Mask BM(8) Read and Write: Bit 7 - Spare Bit 6 - Spare Bit 5 - Output

Page 63

3-18 BE1-700 Modbus™ Protocol 9376700991 Rev D Bit 5 - Spare Bit 4 - Spare Bit 3 - Spare Bit 2 - Spare Bit 1 - Spare Bit 0 - Spare 4128

Page 64

9376700991 Rev D BE1-700 Modbus™ Protocol 3-19 Bit 1 - 159B Bit 0 - 159A 41291-94 Programmable Screen #1 ASC(7) 41295-98 Programmable Screen

Page 65

3-20 BE1-700 Modbus™ Protocol 9376700991 Rev D 47367 System Status (Logic Var 0 to 15) BM(16) Read only: Bit 15 - 50TQ picked-up Bit 14

Page 66

9376700991 Rev D BE1-700 Modbus™ Protocol 3-21 47370 System Status (Logic Var 48 to 63) BM(16) Read only: Bit 15 - Target Reset key Bit

Page 67

9376700991 Rev D BE1-700 Modbus™ Protocol v CONTENTS SECTION 1 • GENERAL INFORMATION ...

Page 68

3-22 BE1-700 Modbus™ Protocol 9376700991 Rev D 47374 Current Group Control Setting ASC(1) Read only: ASCII character 0, 1, L 47375 Curren

Page 69

9376700991 Rev D BE1-700 Modbus™ Protocol 3-23 47381 Active Alarm Flags (Sum Flags) LSBs BM(16) Read only: Bits 15 to 13 - Spare BIT 12

Page 70

3-24 BE1-700 Modbus™ Protocol 9376700991 Rev D Bit 11 - 51B Bit 10 - 51A Bit 9 - 150TQ Bit 8 - 50TQ Bit 7 - 150TN Bit 6 - 50TN Bit 5 - 150TC Bit 4 -

Page 71

9376700991 Rev D BE1-700 Modbus™ Protocol 3-25 Bit 10 - Spare Bit 9 - Spare Bit 8 - Spare Bit 7 - 162 Bit 6 - 62 Bit 5 - 60FL Bit 4 -

Page 72

3-26 BE1-700 Modbus™ Protocol 9376700991 Rev D 47399-400 Breaker Contact Duty Log - Phase A FP 47401-02 Breaker Contact Duty Log - Phase B

Page 73

9376700991 Rev D BE1-700 Modbus™ Protocol 3-27 47472 Peak Demand Since Reset Timestamp - day INT 47477 Peak Demand Since Reset Timestamp - da

Page 74

3-28 BE1-700 Modbus™ Protocol 9376700991 Rev D Bit 6 - 50TN Bit 5 - 150TC Bit 4 - 150TB Bit 3 - 150TA Bit 2 - 50TC Bit 1 - 50TB Bit 0 - 50TA 47520

Page 75

9376700991 Rev D BE1-700 Modbus™ Protocol 3-29 Bit 2 - 59C Bit 1 - 59B Bit 0 - 59A 47523 Fault Targets Fifth MSBs BM(16) Read only: Bit 15

Page 76

3-30 BE1-700 Modbus™ Protocol 9376700991 Rev D 47529-30 Fault Breaker Operate Time FP Read only: 0 if Fault Breaker Operate Time Status is

Page 77

9376700991 Rev D BE1-700 Modbus™ Protocol 3-31 49835-74 Error Details ASC(40) Read only: ASCII string 49875-999 Contiguous Poll Block M

Page 78

vi BE1-700 Modbus™ Protocol 9376700991 Rev D

Page 79

3-32 BE1-700 Modbus™ Protocol 9376700991 Rev D

Page 80

9376700991 Rev D BE1-700 Modbus™ Protocol 4-1 SECTION 4 • ASCII CROSS REFERENCE ASCII Command versus Modbus™ Register Cross Reference ASCII Command

Page 81

4-2 BE1-700 Modbus™ Protocol 9376700991 Rev D ASCII Command Modbus™ Registers RA-MIN=0 47488 RA-REL 47595-47719, 40039 RA-REL=0 47489 RB-DUTYA=<%

Page 82

9376700991 Rev D BE1-700 Modbus™ Protocol 4-3 ASCII Command Modbus™ Registers S#-792=<second auto reclose delay> 40408-40409 S#-793=<third

Page 83

4-4 BE1-700 Modbus™ Protocol 9376700991 Rev D ASCII Command Modbus™ Registers SG-ID=<relay ID>,<station ID> 43438-43452, 43453-43467 SG-

Page 84

9376700991 Rev D BE1-700 Modbus™ Protocol 4-5 ASCII Command Modbus™ Registers SL-381=<mode>,<block logic> 43287, 43288-43293, 43296-4330

Page 85

4-6 BE1-700 Modbus™ Protocol 9376700991 Rev D ASCII Command Modbus™ Registers SN-143=<name>,<true label>,<false label> 43511-43515

Page 86

9376700991 Rev D BE1-700 Modbus™ Protocol A-1 APPENDIX A • SETTING UP A DHCP SERVER BETWEEN BE1-700 AND PC Introduction This appendix explains how t

Page 87 - BETWEEN BE1-700 AND PC

A-2 BE1-700 Modbus™ Protocol 9376700991 Rev D Figure A-2. Global Tab 5. On the DHCP tab, set the IP pool starting address to 10.0.1.100, Size of

Page 88

9376700991 Rev D BE1-700 Modbus™ Protocol A-3 6. Start Tftpd32. Apply power to the BE1-700. Wait approximately 120 seconds for the relay to obtain

Page 89

9376700991 Rev D BE1-700 Modbus™ Protocol i SECTION 1 • GENERAL INFORMATION TABLE OF CONTENTS SECTION 1 • GENERAL INFORMATION ...

Page 90

A-4 BE1-700 Modbus™ Protocol 9376700991 Rev D

Page 92 - Highland IL 62249-1074 USA

12570 State Route 143Highland IL 62249-1074 USAwww.basler.com, [email protected] +1 618.654.2341 Fax +1 618.654.2351®

Comments to this Manuals

No comments