Basler-electric BE1-851 User Manual

Browse online or download User Manual for Relay Basler-electric BE1-851. Basler Electric BE1-851 User Manual

  • Download
  • Add to my manuals
  • Print
  • Page
    / 364
  • Table of contents
  • TROUBLESHOOTING
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews

Summary of Contents

Page 1 - INSTRUCTION MANUAL

INSTRUCTION MANUAL FOR OVERCURRENT PROTECTION SYSTEM BE1-851 Publication: 9289900990 Revision: R 02/14

Page 2

Application Firmware Version and Date Change • Setting groups can be changed during the reclosing sequence by monitoring the 79 shot counter. • Chan

Page 3 - INTRODUCTION

5-2 BE1-851 Metering 9289900990 Rev R

Page 4 - HIGHLAND IL 62249-1074 USA

SECTION 6 • REPORTING AND ALARMS TABLE OF CONTENTS SECTION 6 • REPORTING AND ALARMS ...

Page 5 - REVISION HISTORY

Figure 6-21. BESTlogic Function Element Screen Alarm Reset Logic ... 6-34 Figure 6-22. Settings Compar

Page 6

SECTION 6 • REPORTING AND ALARMS General This section describes all of the reports that are available from the BE1-851 relay, how to set the reporting

Page 7

Clock The BE1-851 provides a real-time clock with capacitor backup that is capable of operating the clock for up to eight hours without power to the r

Page 8

mm/dd/yy or dd/mm/yy format. The default date format is mm/dd/yy. The relay clock can also accommodate daylight saving time changes. Automatic dayligh

Page 9

UTC (Coordinated Universal Time) SG-UTC=M,R,B M (Offset from UTC in Minutes) = -720 to 840 R (Reference Time) = 0 (Local) or 1 (UTC) B (

Page 10

CO-101 (101SC) This line reports the status of the virtual breaker control switch slip-contact output. More information about the virtual breaker cont

Page 11

Table 6-4. Logic Variable Status Report Format for Sensing Input Type G Relays 5 0 TPT 150TPT 50TNT 150TNT 250TNT 350TNT BFT 51PT 51NT 51QT 50TPPU 15

Page 12

this section. As with other commands, a combination read command is available to read several items in a group. If the command RG is entered by itself

Page 13 - CONTENTS

Hardware Version and Date Change Version 3, 11/99 • Label placed on the front panel stating, “WARNING to BESTCOMS USERS: When using BESTCOMS software

Page 14

If the current steps from 0 to 1,000 amperes, then the peak demand will change from 0 to 900 amperes after one demand interval( )ITt=. Each time that

Page 15

Figure 6-3. Reporting and Alarms Screen, Demands Tab Table 6-5. SG-DI Command Settings Setting Range Increment Unit of Measure Default 5 A 1 A Cur

Page 16

next processing loop with the currently calculated demand value. No write access is needed to reset demand register values at the HMI. It is also poss

Page 17 - Features

Figure 6-4. BESTlogic Function Element Screen, Breaker Status Current breaker status can be read from HMI Screen 1.5.6 and through the communication

Page 18

( )operations*#ImaxDerruptint= Equation 6-4. Dmax Set by Number of Operations The setting is in terms of primary amps (the relay multiples by the

Page 19

To connect the functions BLOCK logic input select the Logic button in the Block Accumulation Logic box. The BESTlogic Function Element screen for Brea

Page 20 - Communication

Retrieving Breaker Duty Information Breaker duty values can be read at HMI Screen 4.3.2. Duty values can be changed by using the front panel Edit key.

Page 21 - Primary Applications

Using the pull-down menus and buttons, make the application appropriate settings to the Breaker Alarms function. Table 6-7 summarizes the Breaker Alar

Page 22 - Sample Style Number

Figure 6-8. Protective Fault Analysis Protective element picks upProtective element tripsBreaker auxiliary contact changes stateProtective elem

Page 23 - Operational Specifications

Table 6-8. Legend for Figure 6-8 Call-Out Description A A fault summary report and an oscillographic record are triggered when either the SG-TRIGGER P

Page 24

x BE1-851 Introduction 9289900990 Rev R

Page 25 - General Specifications

Trip Circuit Monitor The trip circuit monitor continually monitors the circuit breaker trip circuit for voltage and continuity. A closed breaker with

Page 26 - Recognition Time

CAUTION Applications that place other device inputs in parallel with the breaker trip coil may not perform as desired. The connection of other devices

Page 27

Pickup Pickup expressions are used by the fault reporting function to time-stamp the fault summary record, time the length of the fault from pickup to

Page 28

Table 6-10. Fault Recording Trigger Settings Setting Purpose Default TRIPPED Logic expression used to define Trip fault reporting condition. When this

Page 29 - SECTION 2 • QUICK START

Setting the Targets Function Targets are enabled using the BESTCOMS screen shown in Figure 6-13. You can select which protective elements trigger a ta

Page 30

The Refresh button is used to refresh the list of faults. The Download button will download the selected fault, storing it on the selected drive as ei

Page 31

Style Number. This line reports the style number of the relay. Firmware Version. This line reports the version of firmware that the relay holds. Faul

Page 32

If the fault report was triggered manually from the View/Download Relay Fault Files screen, the recording of the report was terminated after 60 second

Page 33 - User Interfaces

a 5-cycle buffer is being filled. If the fault is cleared within 5 cycles of the start of the second record, the record is terminated after it has rec

Page 34 - Command Structure

Figure 6-15. View/Download Relay Fault Files Figure 6-16. Browse for Folder Screen Figure 6-17. Fault Record Filenames Only one oscillographic re

Page 35

CONTENTS SECTION 1 • GENERAL INFORMATION ... 1-1 SECTION

Page 36 - Getting Started

Files can be requested in ASCII or binary format, but both file transfers use the same format. Binary file transfer is much faster and consumes less d

Page 37 - Entering General Settings

Retrieving SER Information Using ASCII Commands SER information is retrieved through SER Directory Reports, the New Events Counter, and by obtaining s

Page 38

Table 6-13. Relay Trouble Alarms I.D. # Name Description 1 RAM FAILURE Static RAM read/write error. 2 ROM FAILURE EPROM program memory checksum er

Page 39 - FAQ/Troubleshooting

I.D. # Name Description 10 Q DEMAND ALARM ∗ Negative-sequence unbalance demand. 11 GROUP OVERRIDE ALARM ∗ Setting group control logic override. 12

Page 40

Figure 6-19. Reporting and Alarms Screen, Alarms Tab Table 6-15. Programmable Alarm Settings Setting Range/Purpose Default Major alarm points (dri

Page 41

Figure 6-20. Programmable Alarm Function The status of the three front-panel LEDs (Relay Trouble, Minor Alarm, and Major Alarm) can be read through

Page 42

Figure 6-21. BESTlogic Function Element Screen Alarm Reset Logic BESTlogic™ Elements Controlled by Programmable Alarms Major, Minor, and Logic progr

Page 43 - Current Inputs

Settings Compare BESTCOMS has the ability to compare two different settings files. To use this feature, pull down the Reports menu and select Setting

Page 44

6-36 BE1-851 Reporting and Alarms 9289900990 Rev R

Page 45 - Neutral Current

SECTION 7 • BESTlogic™ PROGRAMMABLE LOGIC TABLE OF CONTENTS SECTION 7 • BESTLOGIC PROGRAMMABLE LOGIC ...

Page 46

xii BE1-851 Introduction 9289900990 Rev R

Page 47

ii BE1-851 BESTlogic™ Programmable Logic 9289900990 Rev R

Page 48

SECTION 7 • BESTlogic™ PROGRAMMABLE LOGIC Introduction Multifunction relays are similar in nature to a panel of single-function protective relays. Bot

Page 49 - Outputs

Figure 7-1. BESTlogic Sensing Input Type G Function Blocks 7-2 BE1-851 BESTlogic™ Programmable Logic 9289900990 Rev R

Page 50 - Programmable Hold Timer

Figure 7-2. BESTlogic Sensing Input Type H Function Blocks 9289900990 Rev R BE1-851 BESTlogic™ Programmable Logic 7-3

Page 51 - Pulsing an Output Contact

Table 7-1. Logic Variable Names and Descriptions for Sensing Input Type H Relays Variable Name Description Variable Name Description Inputs and Output

Page 52

Table 7-2. Logic Variable Names and Descriptions for Sensing Input Type G Relays Variable Name Description Variable Name Description Inputs and Output

Page 53

Function Block Logic Settings Each BESTlogic function block is equivalent to its discrete device counterpart. For example, the Reclosing Logic Functio

Page 54

When the relay is powered up, all logic outputs are disabled and most variables (including virtual outputs) initialize as FALSE. Some variable states

Page 55 - Equations

The BESTlogic Expression Builder provides a point and click interface that allows the selected input to be easily connected using a single OR gate, s

Page 56

Logic schemes can be selected from the Logic Select tab on the BESTlogic Screen. To access this screen, select BESTlogic from the Screens pull-down

Page 57 - Setting Groups

SECTION 1 • GENERAL INFORMATION TABLE OF CONTENTS SECTION 1 • GENERAL INFORMATION ...

Page 58 - AUTOMATIC

CAUTION Always remove the relay from service before changing or modifying the active logic scheme. Attempting a logic scheme change while the relay is

Page 59

Table 7-4. Label Settings for OUTPUTS Setting Range/Purpose Default Label 1 to 10 characters. User label to replace default label. VOx_LABEL (where

Page 60

7-12 BE1-851 BESTlogic™ Programmable Logic 9289900990 Rev R

Page 61

SECTION 8 • APPLICATION TABLE OF CONTENTS SECTION 8 • APPLICATION ...

Page 62

Normal Operation - Reclosing ... 8-35 Normal Op

Page 63

Table 8-6. Feeder_1 Function Block Logic ... 8-11 Table 8-7

Page 64

iv BE1-851 Application 9289900990 Rev R

Page 65

SECTION 8 • APPLICATION General This section discusses application of the BE1-851 Overcurrent Protection System using the pre-programmed logic schemes

Page 66 - Overcurrent Protection

Overview of Preprogrammed Logic Schemes There are six preprogrammed logic schemes available. Four logic schemes are intended for use on feeder breaker

Page 67

Details of Preprogrammed Logic Schemes The following sub-sections describe each of the six preprogrammed logic schemes in detail. For each scheme, th

Page 68

Tables Table 1-1. Contact-Sensing Turn-On Voltages ... 1-10 Table

Page 69

Table 8-2. Factory Default Function Blocks Logic Settings Function Purpose BESTlogic Expression Mode Setting 50TP Used for instantaneous phase overc

Page 70

Table 8-4. Factory Default Virtual Output Logic Settings Output Purpose Description Label State Labels True False VOA (OUTA) Alarm Output Contact.

Page 71

Output Purpose Description Label State Labels True False VO13 N/A N/A VO13_LABEL TRUE FALSE BESTlogic Expression: VO13=0 VO14 N/A N/A VO14

Page 72

Figure 8-2. Factory Default Logic Settings Diagram 9289900990 Rev R BE1-851 Application 8-7

Page 73

Factory Default Logic Settings and Equations for Sensing Input Type H Relays SL-N=USER SL-50TP = 1,0 SL-50TN = 1,0 SL-50TQ = 1,0 SL-150TP = 1,0 SL-150

Page 74

SL-143 = 1 SL-243 = 1 SL-343 = 1 SL-101 = 1 SL-VOA = 0 SL-VO1 = VO11 SL-VO2 = 50TPT SL-VO3 = 51PT SL-VO4 = 50TNT SL-VO5 = 51NT SL-VO6 = 0 SL-VO7 = 0 S

Page 75

When used to provide high-speed overcurrent protection for the substation bus, it is recommended that all 51 function timing curves be set for instant

Page 76 - Breaker Failure Protection

Input Purpose Name Label State Labels Energized De-Energized IN2 Automatic setting group change logic auto/manual switch. SETGRPAUTO ENABLED DISA

Page 77

Table 8-7. Feeder_1 Virtual Switches Logic Switch Purpose Mode Label State Labels True False 43 N/A 0 (Disable) SWITCH_43 CLOSED OPEN 143 N/

Page 78

Output Purpose Description Label State Labels True False VO8 Time overcurrent trip. TRUE if any of the time overcurrent elements trip. 51_TRIP T

Page 79

SECTION 1 • GENERAL INFORMATION General The BE1-851 Overcurrent Protection System is an economical, microprocessor based, multifunction system. It is

Page 80

Figure 8-3. Typical One-Line Diagram for Feeder_1 Logic 8-14 BE1-851 Application 9289900990 Rev R

Page 81 - Mode 5, Integrating Timer

Figure 8-4. Feeder_1 Logic Diagram 9289900990 Rev R BE1-851 Application 8-15

Page 82 - Mode 6, Latch

Feeder_1 Logic Settings and Equations for Sensing Input Type H Relays SL-N=FEEDER_1 SL-50TP = 1,0 SL-50TN = 1,/IN3 SL-50TQ = 1,/IN3 SL-150TP = 0,0 SL-

Page 83

SL-143 = 0 SL-243 = 0 SL-343 = 0 SL-101 = 0 SL-VOA = ALMMAJ SL-VO1 = VO8*IN4+BFPU+VO11*/IN4 SL-VO2 = VO9*IN4 SL-VO3 = IN4 SL-VO4 = VO12*/IN5*IN4 SL-VO

Page 84

cause the recloser to be in lockout. When the breaker is manually closed, the relay will time out to a reset condition. Drive to lockout also occurs i

Page 85

Contingency Operation - Backup Protection for Feeder Breaker Failure OUT5 is configured as the breaker failure trip output. OUT5 can be wired to trip

Page 86 - Recloser Fail Timer (79F)

Function Purpose BESTlogic Expression Mode Setting 50TQ Used for instantaneous negative-sequence overcurrent protection. Block when recloser sequence

Page 87

Table 8-11. Feeder_2 Virtual Switches Logic Switch Purpose Mode Label State Labels True False 43 Automatic setting group change logic auto/manual

Page 88 - Reset Timer (79RST)

Output Purpose Description Label State Labels True False VO5 (OUT5) Breaker failure trip contact. Trip backup if breaker failure protection times

Page 89 - Zone-Sequence Coordination

Figure 8-5. Typical One-Line Diagram for Feeder_2 Logic 9289900990 Rev R BE1-851 Application 8-23

Page 90

Each current sensing circuit is low burden and isolated. Negative-sequence current magnitudes are derived from the three-phase currents. Neutral curre

Page 91

Figure 8-6. Feeder_2 Logic Diagram 8-24 BE1-851 Application 9289900990 Rev R

Page 92

Feeder_2 Logic Settings and Equations for Sensing Input Type H Relays SL-N=FEEDER_2 SL-50TP = 1,79SCB SL-50TN = 1,79SCB+/IN3+243 SL-50TQ = 1,79SCB+/IN

Page 93

SL-143 = 2 SL-243 = 2 SL-343 = 2 SL-101 = 1 SL-VOA = ALMMAJ SL-VO1 = VO11+BFPU+101T SL-VO2 = 79C+101C SL-VO3 = IN4*/343 SL-VO4 = VO12*/VO5*IN4*/343 SL

Page 94

Reclosing can be disabled by IN2 or Virtual Switch 143 that is connected to the drive to lockout (DTL) input of the recloser function block. In this

Page 95

be controlled by a pole of a standard external test switch that is opened with the rest of the test switch poles. The logic expression for test mode d

Page 96

Table 8-14. Feeder_3 Function Block Logic Function Purpose BESTlogic Expression Mode Setting 50TP Used for instantaneous phase overcurrent protection

Page 97 - SECTION 5 • METERING

Table 8-15. Feeder_3 Virtual Switches Logic Switch Purpose Mode Label State Labels True False 43 Automatic setting group change logic auto/manual

Page 98

Output Purpose Description Label State Labels True False VO5 (OUT5) Breaker failure trip contact. Trip backup if breaker failure protection times

Page 99

Figure 8-7. Typical One-Line Diagram for Feeder_3 Logic 8-32 BE1-851 Application 9289900990 Rev R

Page 100

Figure 8-8. Feeder_3 Logic Diagram 9289900990 Rev R BE1-851 Application 8-33

Page 101 - TABLE OF CONTENTS

Metering Metering is provided for all measured currents, and all derived neutral and negative-sequence currents. One percent meter accuracy is provide

Page 102

Feeder_3 Logic Settings and Equations for Sensing Input Type H Relays SL-N=FEEDER_3 SL-50TP = 1,79SCB SL-50TN = 1,79SCB+/IN3+243 SL-50TQ = 1,79SCB+/IN

Page 103 - Relay Identifier Information

SL-143 = 2 SL-243 = 2 SL-343 = 2 SL-101 = 1 SL-VOA = ALMMAJ SL-VO1 = VO11+BFPU+101T SL-VO2 = 79C+101C SL-VO3 = IN4*/343 SL-VO4 = VO12*/VO5*IN4*/343 SL

Page 104 - Setting the Clock Function

Reclosing can be disabled by IN2 or Virtual Switch 143 that interrupts the RI input to the recloser function block. In this scheme, enabling the reclo

Page 105

Contingency Operation - Backup Protection for Feeder Breaker Failure OUT5 is configured as the breaker failure trip output. OUT5 can be wired to trip

Page 106 - General Status Reporting

Function Purpose BESTlogic Expression Mode Setting 50TQ Used for instantaneous negative-sequence overcurrent protection. Block when recloser sequence

Page 107 - CO-Group

Table 8-19. Feeder_4 Virtual Switches Logic Switch Purpose Mode Label State Labels True False 43 Automatic setting group change logic auto/manual

Page 108 - Other RG Commands

Output Purpose Description Label State Labels True False VO5 (OUT5) Breaker failure trip contact. Trip backup if breaker failure protection times

Page 109 - 15 seconds)

Figure 8-9. Typical One-Line Diagram for Feeder_4 Logic 9289900990 Rev R BE1-851 Application 8-41

Page 110 - Setting Demand Reporting

Figure 8-10. Feeder_4 Logic Diagram 8-42 BE1-851 Application 9289900990 Rev R

Page 111

Feeder_4 Logic Settings and Equations for Sensing Input Type H Relays SL-N=FEEDER_4 SL-50TP = 1,79SCB SL-50TN = 1,79SCB+243 SL-50TQ = 1,79SCB+243 SL-1

Page 113 - Breaker Duty Monitoring

output contact including OUTA. Over 20 alarm conditions are available to be monitored including user definable logic conditions using BESTlogic. Activ

Page 114

SL-143 = 2 SL-243 = 2 SL-343 = 2 SL-101 = 1 SL-VOA = ALMMAJ SL-VO1 = VO11+BFPU+101T SL-VO2 = 79C+101C SL-VO3 = /79SCB SL-VO4 = VO12*/VO5*IN4*/343 SL-V

Page 115

interrupt the fault. These are set up to trip the 86B relay also via OUT4. If a bus fault lockout relay is not used, OUT4 can be wired in parallel wit

Page 116 - Breaker Alarms

This function block has an independent fast drop out phase and ground current detector that detects a breaker opening and stops timing. An open breake

Page 117

Table 8-21. BUS Contact Sensing Input Logic Input Purpose Name Label State Labels Energized De-Energized IN1 52b Breaker Status. BREAKER OPEN C

Page 118 - 07-22-05

Table 8-23. BUS Virtual Switch Logic Switch Purpose Mode Label State Labels True False 43 N/A 0 (Disable) SWITCH_43 CLOSED OPEN 143 N/A 0

Page 119

Output Purpose Description Label State Labels True False VO5 (OUT5) Feeder breaker trip. Trip feeder breaker via auxiliary relay (94) for time (51

Page 120 - Trip Circuit Monitor

Figure 8-11. Typical One-Line Diagram for BUS Logic 8-50 BE1-851 Application 9289900990 Rev R

Page 121 - Fault Reporting

Figure 8-12. BUS Logic Diagram 9289900990 Rev R BE1-851 Application 8-51

Page 122

BUS Logic Settings and Equations for Sensing Input Type H Relays SL-N=BUS SL-50TP = 1,IN2 SL-50TN = 1,IN2 SL-50TQ = 1,IN2 SL-150TP = 0,0 SL-150TN = 0,

Page 123 - Targets

SL-143 = 0 SL-243 = 0 SL-343 = 2 SL-101 = 1 SL-VOA = ALMMAJ SL-VO1 = 101T+VO8*/SG0+62*SG1+VO11*VO15 SL-VO2 = 101C SL-VO3 = 0 SL-VO4 = VO9*SG0*/VO15 SL

Page 124 - Fault Summary Reports

BESTCOMS™ Software BESTCOMS is a Windows® based graphical user interface (GUI) that runs on IBM-compatible computers. The software is used to create s

Page 125 - Fault Summary Report Example

Function Purpose BESTlogic Expression Mode Setting 51P Used for timed phase overcurrent protection. 0 1 (enabled) 51N Used for timed neutral over

Page 126

Table 8-28. BACKUP Virtual Outputs Output Purpose Description Label State Labels True False VOA (OUTA) Alarm Output Contact. Change state of alarm

Page 127 - Oscillographic Records

Output Purpose Description Label State Labels True False VO11 Protective Trip Expression. TRUE when any 50 or 51 element times out. PROT_TRIP TRI

Page 128

Figure 8-13. Typical One-Line Diagram for Backup Logic 9289900990 Rev R BE1-851 Application 8-57

Page 129

Figure 8-14. BACKUP Logic Diagram 8-58 BE1-851 Application 9289900990 Rev R

Page 130 - Sequence of Events Recorder

BACKUP Logic Settings and Equations for Sensing Input Type H Relays SL-N=BACKUP SL-50TP = 1,0 SL-50TN = 1,0 SL-50TQ = 1,0 SL-150TP = 1,0 SL-150TN = 1,

Page 131 - Alarms Function

SL-143 = 0 SL-243 = 0 SL-343 = 2 SL-101 = 1 SL-VOA = ALMMAJ SL-VO1 = 101T+VO8+BFPU+VO11*VO15 SL-VO2 = 101C SL-VO3 = /IN2 SL-VO4 = VO9*/VO15 SL-VO5 = B

Page 132

Miscellaneous Logic Settings There are five logic variables that are classified as miscellaneous logic expressions. These expressions are: SG-TARG, SG

Page 133 - Programming Alarm Priorities

detect when the relay is out of service for test. This enables the backup logic and enhances security. It should be noted that if the test mode logic

Page 134

High-Speed Reclose Each reclose time delay can be set as low as 100 milliseconds. If the application requires a reclose time delay of less than 250 mi

Page 135 - Programmable Alarms Reset

Model and Style Number Description General The BE1-851 Overcurrent Protection System electrical characteristics and operational features are defined b

Page 136

However, distribution systems with single pole fault clearing and switching devices or long single-phase laterals may have mis-operations during switc

Page 137 - Settings Compare

Figure 8-19. Output Seal-In Logic Diagram NOTE This example is based on the Feeder_2, Feeder_3, or Feeder_4 preprogrammed logic schemes. Table 8-30

Page 138

8-66 BE1-851 Application 9289900990 Rev R

Page 139

SECTION 9 • SECURITY TABLE OF CONTENTS SECTION 9 • SECURITY ...

Page 140

ii BE1-851 Security 9289900990 Rev R

Page 141 - Introduction

SECTION 9 • SECURITY Introduction In this section, security, in the form of multilevel password protection, is discussed along with the information re

Page 142

Figure 9-1. General Operation Screen, Global Security Tab If a change is required and the Password Security box reads Show Passwords, press Show Pas

Page 143

Table 9-1 lists password protection settings. Table 9-1. Password Protection Settings Setting Range/Purpose Password User defined alphanumeric strin

Page 144

9-4 BE1-851 Security 9289900990 Rev R

Page 145

SECTION 10 • HUMAN-MACHINE INTERFACE TABLE OF CONTENTS SECTION 10 • HUMAN-MACHINE INTERFACE ...

Page 146 - Defining Output Operation

Operational Specifications BE1-851 relays have the following features and capabilities. Metered Current Values and Accuracy Current Range ...

Page 147 - BESTlogic Expression Builder

ii BE1-851 Human-Machine Interface 9289900990 Rev R

Page 148 - Logic Schemes

SECTION 10 • HUMAN-MACHINE INTERFACE General This section provides a description of the BE1-851 human-machine interface and illustrates the menu tree.

Page 149 - Custom Logic Schemes

Locator Description D, E Minor Alarm and Major Alarm LEDs - When these LEDs are ON, it indicates a minor or major alarm status. Refer to Section 6,

Page 150 - Debugging the Logic Scheme

Figure 10-3. Report Status Branch Menu Tree Figure 10-4. Control and Metering Branches Menu Tree 9289900990 Rev R BE1-851 Human-Machine I

Page 151 - BESTlogic™ Application Tips

Figure 10-5. Reports Branch Menu Tree 10-4 BE1-851 Human-Machine Interface 9289900990 Rev R

Page 152

Figure 10-6. Protection Logic Branch Menu Tree for Sensing Input Type H Relays 9289900990 Rev R BE1-851 Human-Machine Interface 10-5

Page 153 - SECTION 8 • APPLICATION

Figure 10-7. Protection Logic Branch Menu Tree for Sensing Input Type G Relays 10-6 BE1-851 Human-Machine Interface 9289900990 Rev R

Page 154

Figure 10-8. General Settings Branch Menu Tree Automatic HMI Display Priorities If no front panel-scrolling key has been pressed for approximately f

Page 155

Once the user has taken manual control of the display by pressing any of the scrolling pushbuttons, automatic priority has been disabled until the dis

Page 156

details on entering passwords from the HMI. Once access has been gained, the Edit LED will be lighted and a cursor will appear in the first settings f

Page 157

50BF Breaker Failure Protection Pickup Setting Range ... Fixed at 0.5 A for 5 A unit, 0.

Page 158

Table 10-3. Call-out Descriptions for Figure 10-10 Locator Description A This is the screen number. It eases navigation by indicating the current bra

Page 159 - Operations - Alarms

SECTION 11 • ASCII COMMAND INTERFACE TABLE OF CONTENTS SECTION 11 • ASCII COMMAND INTERFACE ...

Page 160

ii BE1-851 ASCII Command Interface 9289900990 Rev R

Page 161 - True False

SECTION 11 • ASCII COMMAND INTERFACE Introduction Relay and power system information can be retrieved from a remote location using the ASCII command i

Page 162

General command functions are organized into five major groups plus one group of miscellaneous commands. These groups are listed below: CONTROL (C):

Page 163

Miscellaneous Command Descriptions HELP Command The HELP (H) command provides general information on command syntax and functionality when the manual

Page 164

ACCESS Command Examples: 1. A valid password is entered. Sent: ACCESS=OPENUP Received: ACCESS GRANTED : GLOBAL 2. An invalid password is ente

Page 165 - Feeder_1 Logic Scheme

The S command returns the values of relay setting parameters in the same form that they are programmed. It can be used at the end of a programming ses

Page 166 - Normal Operation - Alarms

SG-FREQ=60 SG-HOLDA=0; SG-HOLD1=1; SG-HOLD2=1; SG-HOLD3=0 SG-HOLD4=0; SG-HOLD5=1 SG-ID=BE1-851,SUBSTATION_1

Page 167

Entering SL by itself returns all of the logic equations associated with the active logic scheme. Entering SL: returns the names of all available logi

Page 168

General Specifications AC Current Inputs 5 Ampere CT Continuous Rating ... 20 A One Second Rati

Page 169

Table 11-1. Communication Settings Parameter Description Range Default Baud Baud Rate 300, 600, 1200, 2400, 4800, 9600, or 19K 9600 A Address for

Page 170

EXIT Command Purpose: Exit programming mode Syntax: EXIT - Note: Relay will prompt for verification Example: EXIT Reference: Section 11, ASCII

Page 171

RB Command Purpose: Read breaker status Syntax: RB Example: RB Reference: Section 6, Reporting and Alarms, Breaker Monitoring RB-DUTY Command P

Page 172

RG Command Purpose: Report General Information Syntax: RG Example: RG Reference: Section 6, Reporting and Alarms, Clock RG-DATE Command Purpose

Page 173 - Feeder_2 Logic Scheme

RS Command Purpose: Read/Reset Sequence of Events Record Data Syntax: RS[-n/Fn/ALM/IO/LGC/NEW][=0] where n=# of events and Fn=fault record # Examp

Page 174

SA-MIN Command Purpose: Read/Set minor alarm setting mask Syntax: SA-MIN[={alarm num 1}[/{alarm num 2}]...[/{alarm num n}]] Example: SA-MIN or S

Page 175

SG-DATADUMP Command Purpose: Report/Set fault record DATADUMP to COM1 Syntax: SG-DATADUMP[={mode}] where mode is 0/1 (disabled/enabled) Example:

Page 176

SG-IN Command Purpose: Read/Set Input recognition/debounce Syntax: SG-IN[#[={r(ms)},{db(ms)}]] where ms=1-255msec Example: SG-IN or SG-IN3 or SG

Page 177

SL-101 Command Purpose: Read/Set Logic for Virtual Breaker switch (101) Syntax: SL-101[=mode] where mode=0/1 (disabled/enabled) Example: SL-101

Page 178

SL-VO Command Purpose: Read/Set Output Logic Syntax: SL-VO[x[={Boolean equation}]] where x is 1 - 15 or A Example: SL-VO or SL-VO1=50TPT+50TNT+5

Page 179

Contact-Sensing Inputs Turn-On Voltage Contact-sensing turn-on voltages are listed in Table 1-1. Table 1-1. Contact-Sensing Turn-On Voltages Style Op

Page 180

SP-79ZONE Command Purpose: Read/Set 79 Zone Sequence Logic Syntax: SP-79ZONE[={zone pickup logic}] Example: SP-79ZONE or SP-79ZONE=50TPPU+50TNPU

Page 181

SECTION 12 • INSTALLATION TABLE OF CONTENTS SECTION 12 • INSTALLATION ...

Page 182 - Feeder_3 Logic Scheme

Table 12-3. RS-485 Pin-outs (COM2) ... 12-22 Table 12-

Page 183

SECTION 12 • INSTALLATION General BE1-851 Overcurrent Protection Systems are delivered with this instruction manual and BESTCOMS™ software in a sturdy

Page 184

installed at the factory, one pin should be visible when viewed from the side of the unit. This configuration allows the inputs to Operate at the high

Page 185

Figure 12-2. S1 Case, Overall Dimensions Edit ResetRelay Minor MajorPower Trouble Alarm Alarm TripOvercurrent RelayBE1-851RCom 0Serial PortSTYLE NUMB

Page 186

Figure 12-3. S1 Case, Cutout Dimensions 12-4 BE1-851 Installation 9289900990 Rev R

Page 187

Figure 12-4. S1 Case, Adapter Plate (FT32 Opening to S1 Case) 9289900990 Rev R BE1-851 Installation 12-5

Page 188

Figure 12-5. S1 Case, Adapter Plate (S2 and FT2 Opening to S1 Case) 12-6 BE1-851 Installation 9289900990 Rev R

Page 189

Figure 12-6. H1 Case, Overall Dimensions 9289900990 Rev R BE1-851 Installation 12-7

Page 190

Real-Time Clock Accuracy ... 1 second per day at 25°C (free running) or ±2 milli

Page 191 - Feeder_4 Logic Scheme

Figure 12-7. H1 Case, Single Relay Mounting Plate Dimensions Figure 12-8. H1 Case, Single Relay Mounting Dimensions for Panel Mounting without an

Page 192

Figure 12-9. H1 Case, Two-Relay Mounting Plate Dimensions 9289900990 Rev R BE1-851 Installation 12-9

Page 193

Figure 12-10. H1 Case, Two-Relay Mounting Dimensions for Panel Mounting without an Escutcheon Plate 12-10 BE1-851 Installation 9289900990 Rev R

Page 194

Figure 12-11. Adapter Bracket for Mounting a Single Relay in a 19-inch Rack Figure 12-12. Adapter Bracket for 19-inch Rack Mount with ABB FT

Page 195

Figure 12-13. F1 Case, Overall Dimensions Com 0Serial PortEdit ResetRelay Minor MajorPower Trouble Alarm Alarm TripOvercurrent RelayBE1-851Style Numb

Page 196

Figure 12-14. F1 Case, Cutout Dimensions Dovetailing Procedure Basler H1 cases can be interlocked by means of a tenon and mortise on the left and ri

Page 197

Step 6: Position the rear panel on the case from which it was removed. Make sure that the panel orientation is correct. Perform Step 6a if Terminal S

Page 198

Figure 12-16. F1 Case, Rear View, Terminal Connections A4 A5A1 A2 A3 A6 A7 A8-IN1+ +IN2-+IN3- -IN4+IRIG+-PWRCABRS-485GNDCOM 2(618) 654-2341H

Page 199

Figure 12-17. H1 Case, Rear View, Terminal Connections Figure 12-18. S1 Case, Rear View, Terminal Connections I IINICIBIANCBAIID2 D4D6 D8D7D5D3D1IR

Page 200 - Bus and Backup Logic Schemes

Typical DC and AC Connections Typical external DC and AC connections for the BE1-851 are shown in Figures 12-19 and 12-20. Figure 12-19. Typ

Page 201

Environment Temperature Operating Range ... −40°C to 70°C (−40°F to 158°F) Storage Range ...

Page 202

Figure 12-20. Typical DC Connection Diagram 12-18 BE1-851 Installation 9289900990 Rev R

Page 203

Terminal Blocks There are two sizes of terminal blocks used on the H1 case design, the current circuit block and the input-output blocks. The current

Page 204

Table 12-2. RS-232 Pin-outs (COM0 and COM1) Name Function Name Direction 1 Shield ---- N/A 2 Transmit Data (TXD) From relay 3 Receive Data

Page 205

Figure 12-22. Personal Computer to BE1-851 (Straight Cable) Figure 12-23. Modem to BE1-851 (Null Modem Cable) 54321 12345RXDTXDSGNDTXDRXDN.C.SGNDFE

Page 206

RS-485 Connector The RS-485 connector is a three-position terminal block connector designed to interface to a standard communication cable. A twisted-

Page 207

Table 12-4. IRIG Pin-outs Terminal Function A1 (+) Signal A2 (-) Reference Terminal Assignments Figure 12-25 illustrates the location of the IRIG

Page 208

Updating is not required if a new style insertion guide (Figure 12-27) is present. Figure 12-27. Insertion Guide - New Style The following procedur

Page 209

SECTION 13 • TESTING AND MAINTENANCE TABLE OF CONTENTS SECTION 13 • TESTING AND MAINTENANCE ...

Page 210

ii BE1-851 Testing and Maintenance 9289900990 Rev R

Page 211

SECTION 13 • TESTING AND MAINTENANCE General You may prefer to test your relay before installation. To verify functionality of the BE1-851 relay, perf

Page 212

SECTION 2 • QUICK START TABLE OF CONTENTS SECTION 2 • QUICK START ...

Page 213

Power-Up Step 1: Apply voltage to Power Terminals A6 and A7. Table 13-1 shows the appropriate voltage for each style of relay. Table 13-1. Relay Vol

Page 214

Table 13-2. Contact Sensing Turn-On Voltage Nominal Control Voltage Contact Sensing Turn-On Voltage Jumper Installed (Low Position) Jumper Not Install

Page 215

Step 2: Transmit the appropriate command from Table 13-4 to program the 50T pickup setting. Table 13-4. Pickup Settings Style Number Commands Phase

Page 216

Step 7: After pickup occurs, ramp the current down slowly until OUT1 opens. Dropout should occur at 90% ±2% of the pickup current magnitude. Step 8:

Page 217 - Application Tips

Table 13-10. Pickup Settings Style Number Commands Phase Neutral x1xxxxx S0-51P=0.1A,0m S0-51N=0.1A,0m x3xxxxx S0-51P=0.5A,0m S0-51N=0.1A,0m x5xx

Page 218 - Close Circuit Monitor

Table 13-14. Pickup Settings Style Number Commands Phase Neutral x1xxxxx S0-51P=3.2A,0m S0-51N=3.2A,0m x3xxxxx S0-51P=16.0A,0m S0-51N=3.2A,0m x5x

Page 219 - Block Load Tap Changer

Table 13-16. Pickup and Timer Settings Style Number Commands Phase Neutral x1xxxxx S0-50TP=1.0A,0.0m S0-50TN=1.0A,0.0m x3xxxxx S0-50TP=5.0A,0.0m

Page 220 - Output Contact Seal-In

Table 13-19. Timing Ranges Style Number Current/Frequency Timing Range Phase Neutral Low Limit High Limit x1xxxxx 5.0A/50 Hz 5.0A/50 Hz 0.0 sec

Page 221

51 Timings Step 1: Transmit the following scheme to the relay: ACCESS=851 SL-N=NONE YES SL-N=TIME51 SL-51=1,0 SL-

Page 222

Table 13-24. Command Settings Style Number Commands Phase Neutral x1xxxxx S0-51P=0.1A,5.0,I2 S0-51N=0.1A,5.0,I2 x3xxxxx S0-51P=0.5A,5.0,I2 S0-51N

Page 223 - SECTION 9 • SECURITY

INTRODUCTION This instruction manual provides information about the operation and installation of the BE1-851 Overcurrent Protection System. To accomp

Page 224

ii BE1-851 Quick Start 9289900990 Rev R

Page 225

Table 13-27. Timing Ranges Style Number Current Low Limit High Limit x1xxxxx 0.2 amps 8.300 sec 9.172 sec x1xxxxx 1.0 amps 2.493 sec 2.755 se

Page 226

Figure 13-2. Backup Battery Location WARNING! Do not short-circuit, reverse battery, or attempt to recharge the battery. Step 4: Insert the new

Page 227

Updating Relay Firmware If a firmware upgrade is desired, contact Basler Electric technical support to request download access. Once the appropriate f

Page 228

SECTION 14 • BESTCOMS™ SOFTWARE TABLE OF CONTENTS SECTION 14 • BESTCOMS™ SOFTWARE ...

Page 229

Figure 14-15. Logic Timers Screen ... 14-12 Figure

Page 230

SECTION 14 • BESTCOMS™ SOFTWARE Description BESTCOMS is a Windows® based program that runs on an IBM compatible computer and provides a user friendly

Page 231 - Front Panel Display

Figure 14-1. Typical User Interface Components Installation BESTCOMS for BE1-851 Software contains a setup utility that installs the program on your

Page 232 - Menu Tree

Updating BESTCOMS™ Software Future enhancements to relay functionality may make firmware update desirable. Enhancements to relay firmware typically co

Page 233

Figure 14-3. System Setup Summary Screen Configure the PC If you have an actual BE1-851 relay, configure your PC to match the BE1-851 configuration.

Page 234

Overcurrent Screen. Pull down the Screens menu and select Overcurrent. If you wanted the specific setting change that you were about to make to affe

Page 235

SECTION 2 • QUICK START General This section provides an overview of the BE1-851 Overcurrent Protection System. You should be familiar with the concep

Page 236

Figure 14-5. General Operation Screen, Power System Tab Global Security Each of three communication ports and the four functional areas (Global, Set

Page 237

Figure 14-6. General Operation Screen, Global Security Tab Communication This tab (see Figure 14-7) allows the user to set or change communication po

Page 238 - HMI Operations

HMI Display This tab (see Figure 14-8) allows the user to change the screen scroll list. Only the code for the latest version of BESTCOMS is containe

Page 239 - Entering Passwords

Figure 14-9. Setting Group Selection Screen Overcurrent Pull down the Screens menu and select Overcurrent or click on the Overcurrent protection icon

Page 240 - Resetting Functions

If you want to change the characteristic curve constants, select the Curve Coefficients and a dialog box opens for those entries. See Figure 14-11.

Page 241

Reclosing Pull down the Screens menu and select Reclosing or click on the Reclosing icon that is shown at the right margin of this paragraph. This scr

Page 242

Logic settings for the breaker failure function can be made by clicking on the BESTlogic button and with your custom logic selected, select the mode a

Page 243 - ASCII Command Interface

Logic settings for the logic timers can be made by clicking on the BESTlogic button and with your custom logic selected, use the Mode pull-down menu a

Page 244 - Command Text File Operations

Figure 14-17. Reporting and Alarms Screen, Demands Tab Breaker Monitoring Each time the breaker trips, the breaker duty monitor updates two sets of

Page 245 - ACCESS Command

Use the Breaker Duty Monitoring pull-down menu to select the operating Mode. Click in the field for 100% Duty Maximum and set the value. Logic settin

Page 246 - Reading All Settings

Figure 2-1. 79 Reclosing Function Block Four inputs: • RI (reclose initiate) • STATUS (breaker position) • WAIT • DTL/BLK (drive to lockout/bloc

Page 247

Figure 14-20. Reporting and Alarms Screen, Fault Recording Tab Logic settings for the Target Reset Logic can be made by clicking on the Target Reset

Page 248 - Reading Logic Settings

Figure 14-21. Inputs and Outputs Screen, Inputs 1 – 4 Tab Outputs 1 – 5, A On this tab (see Figure 14-22), the only feature that you may change is t

Page 249

Virtual Switches Pull down the Screens menu and select Virtual Switches or click on the Virtual Switches icon that is shown at the right margin of thi

Page 250 - Command Summary

Figure 14-24. BESTlogic Screen, Logic Select Tab Virtual Outputs You can assign a meaningful name or label to each virtual output. This makes sequent

Page 251 - Report Commands

Function Blocks Not all of the logic functions have BESTlogic labeled on the button. If the logic function is labeled Logic and not BESTlogic, the ASC

Page 252

Downloading Oscillography Files To download an oscillography file, pull down the Reports menu from the Pull-down menu as shown in Figure 14-28 and

Page 253

dialog box has two pull-down menus: File and Communication. To configure communication with the relay, pull down the Communication menu and select

Page 254 - Alarm Setting Commands

Opening a Settings File To open a settings file into BESTCOMS, pull down the File menu and choose Open. If the settings in your BESTCOMS have changed,

Page 255 - General Setting Commands

Figure 14-31. Settings Compare Setup Dialog Box If there are any differences in the two files, a dialog box will appear and notify you that differen

Page 256

APPENDIX A • TIME OVERCURRENT CHARACTERISTIC CURVES TABLE OF CONTENTS APPENDIX A • TIME OVERCURRENT CHARACTERISTIC CURVES ...

Page 257

to be mode 1 (enabled) with the function blocked when contact sensing INput 2 is not (/) energized. Contact sensing input 2 would be wired to a gro

Page 258

ii BE1-851 Time Overcurrent Characteristic Curves 9289900990 Rev R

Page 259 - Protection Setting Commands

APPENDIX A • TIME OVERCURRENT CHARACTERISTIC CURVES General Basler Electric inverse time overcurrent systems (ANSI Device 51) provide time/current cha

Page 260 - Global Commands

Table A-1. 51P, 51N, and 51Q Time Characteristic Curve Constants Curve Selection Curve Name Trip Characteristic Constants Reset † A B C N K R S1

Page 261 - SECTION 12 • INSTALLATION

Table A-2. Characteristic Curve Cross-Reference Curve Curve Name Similar To S1 Short Inverse ABB CO-2 S2 Short Inverse GE IAC-55 L1 Long Inverse AB

Page 262

coordination is tight, it is recommended that you retrofit your circuits with Basler Electric electronic relays to ensure high timing accuracy. Table

Page 263

Figure A-1. Time Characteristic Curve S1, Short Inverse (Similar to ABB CO-2) 9289900990 Rev R BE1-851 Time Overcurrent Characteristic Curves A-5

Page 264 - Mounting

Figure A-2. Time Characteristic Curve S2, Short Inverse (Similar To GE IAC-55) A-6 BE1-851 Time Overcurrent Characteristic Curves 9289900990 Rev R

Page 265 - Overcurrent Relay

Figure A-3. Time Characteristic Curve L1, Long Inverse (Similar to ABB CO-5) 9289900990 Rev R BE1-851 Time Overcurrent Characteristic Curves A-7

Page 266

Figure A-4. Time Characteristic Curve L2, Long Inverse (Similar To GE IAC-66) A-8 BE1-851 Time Overcurrent Characteristic Curves 9289900990 Rev R

Page 267

Figure A-5. Time Characteristic Curve D, Definite Time (Similar To ABB CO-6) 9289900990 Rev R BE1-851 Time Overcurrent Characteristic Curves A-9

Page 268

menu tree top level. You view each branch of the menu tree by using the RIGHT and LEFT scrolling pushbuttons. To go to a level of greater detail,

Page 269

Figure A-6. Time Characteristic Curve M, Moderately Inverse (Similar to ABB CO-7) A-10 BE1-851 Time Overcurrent Characteristic Curves 9289900990 R

Page 270 - D2875-19

Figure A-7. Time Characteristic Curve I1, Inverse Time (Similar to ABB CO-8) 9289900990 Rev R BE1-851 Time Overcurrent Characteristic Curves A-11

Page 271

Figure A-8. Time Characteristic Curve I2, Inverse Time (Similar to GE IAC-51) A-12 BE1-851 Time Overcurrent Characteristic Curves 9289900990 Rev R

Page 272 - without an Escutcheon Plate

Figure A-9. Time Characteristic Curve V1, Very Inverse (Similar to ABB CO-9) 9289900990 Rev R BE1-851 Time Overcurrent Characteristic Curves A-13

Page 273 - 9289924100

Figure A-10. Time Characteristic Curve V2, Very Inverse (Similar to GE IAC-53) A-14 BE1-851 Time Overcurrent Characteristic Curves 9289900990 Rev

Page 274

Figure A-11. Time Characteristic Curve E1, Extremely Inverse (Similar to ABB CO-11) 9289900990 Rev R BE1-851 Time Overcurrent Characteristic Curves

Page 275 - Dovetailing Procedure

Figure A-12. Time Characteristic Curve E2, Extremely Inverse (Similar to GE IAC-77) A-16 BE1-851 Time Overcurrent Characteristic Curves 9289900990

Page 276 - Relay Connections

Figure A-13. Time Characteristic Curve A, Standard Inverse 9289900990 Rev R BE1-851 Time Overcurrent Characteristic Curves A-17

Page 277 - 03-10-06

Figure A-14. Time Characteristic Curve B, Very Inverse A-18 BE1-851 Time Overcurrent Characteristic Curves 9289900990 Rev R

Page 278 - Basler Electric

Figure A-15. Time Characteristic Curve C, Extremely Inverse 9289900990 Rev R BE1-851 Time Overcurrent Characteristic Curves A-19

Page 279 - D2569-04

the object names. Most commands don't require that you specify a complete object name. If the first two letters of a command are entered, the rel

Page 280

Figure A-16. Time Characteristic Curve G, Long Time Inverse A-20 BE1-851 Time Overcurrent Characteristic Curves 9289900990 Rev R

Page 281 - Communication Connections

APPENDIX B • COMMAND CROSS-REFERENCE TABLE OF CONTENTS APPENDIX B • COMMAND CROSS-REFERENCE ...

Page 282

ii BE1-851 Command Cross-Reference 9289900990 Rev R

Page 283 - 02-19-97

APPENDIX B • COMMAND CROSS-REFERENCE Introduction This appendix lists all ASCII commands, command syntax, brief command descriptions, and any correspo

Page 284 - IRIG Input and Connections

ASCII Command Function HMI Screen RB-OPCNTR[={#operations}] Read/Set breaker operation counter. 4.3.1 RD Report all demand data. N/A RD-PI[[=

Page 285 - Terminal Assignments

ASCII Command Function HMI Screen SG-CT[t][={CT_ratio}] Read/Set Phase/Neutral CT ratio. 6.3.1 SG-DIPage[={interval}] Read/Set P(IA/IB/IC/var/watt)

Page 286 - Procedure

Table B-10. User Programmable Name Setting Command ASCII Command Function HMI Screen SN[-{var}[={name},{TRUE label},{FALSE label}] Read/Set user prog

Page 287

APPENDIX C • TERMINAL COMMUNICATION TABLE OF CONTENTS APPENDIX C • TERMINAL COMMUNICATION ...

Page 288

ii BE1-851 Terminal Communication 9289900990 Rev R

Page 289

APPENDIX C • TERMINAL COMMUNICATION HyperTerminal (provided with Windows 2000/XP) or other stand-alone software can be used to communicate with a BE1

Page 290 - Communications

Getting Started Refer to Section 12, Installation, for typical external connection diagrams. If your relay has power supply option 1 or 2, it can be s

Page 291 - Pickup and Dropout Testing

Figure C-2. Connect To Dialog Box Step 6: Dialog Box: COMx Properties a. Make the following selections using Figure C-3 as a guide: Set the bits p

Page 292

Step 7: Click File/Properties on the menu bar. Click the Settings tab. a. Make the following selections using Figure C-4 as a guide: Check the Termi

Page 293 - 51 Pickups and Dropouts

Figure C-5. ASCII Setup Dialog Box Step 9: HyperTerminal is now ready to communicate with the relay. Table C-1 describes the required connection f

Page 295 - Timings

12570 State Route 143 Highland IL 62249-1074 USA Tel: +1 618.654.2341 Fax: +1 618.654.2351 email: [email protected] P.A.E. Les Pins 67319 Wasselonne

Page 296

Figure 2-3. File Properties Screen Entering General Settings Time and date format can be changed by selecting Reporting and Alarms from the Screens m

Page 297

Using the pull-down menus and buttons located on the Power System tab, select the appropriate phase and neutral CT ratios, the system's nominal f

Page 298 - 51 Timings

Use the remaining screens and associated tabs to make additional settings required for evaluation of the relay. Save the file. From the Communication

Page 299

First Printing: March 1997 Printed in USA Copyright © 2014 Basler Electric, Highland Illinois 62249 USA All Rights Reserved February 2014 CONFIDE

Page 300 - Maintenance

needed. To read data or to get any reports this can be done without gaining access. After gaining access though one of the ports a session can be ende

Page 301 - Storage

SECTION 3 • INPUT AND OUTPUT FUNCTIONS TABLE OF CONTENTS SECTION 3 • INPUT AND OUTPUT FUNCTIONS ...

Page 302 - Updating BESTCOMS™ Software

ii BE1-851 Input and Output Functions 9289900990 Rev R

Page 303

SECTION 3 • INPUT AND OUTPUT FUNCTIONS General The BE1-851 inputs consist of three-phase current inputs, neutral current inputs, and four contact sens

Page 304

Figure 3-1. Accuracy Characteristics, 55 to 65 Hz The Average setting uses a digital measurement circuit. This circuit consists of a full wave recti

Page 305 - Description

Negative-Sequence Current Negative-Sequence components are measured from the fundamental component of the three-phase current inputs. The relay can be

Page 306 - Installation

Figure 3-3. General Operation Screen, Power System Tab Contact-Sensing Inputs BE1-851 relays have four contact-sensing inputs to initiate BE1-851 re

Page 307 - Starting BESTCOMS™

Digital Input Conditioning Function Status of the contact sensing inputs is checked 24 times per cycle. When operating on a 60 Hz power system, this r

Page 308 - Setting the Relay

If you are concerned about ac voltage being coupled into the contact sensing circuits, the recognition time can be set to greater than one-half of the

Page 309 - Power System

Outputs BE1-851 relays have five general-purpose output contacts (OUT1 through OUT5) and one fail-safe, normally open/normally closed, alarm output co

Page 310 - Global Security

REVISION HISTORY The following information provides a historical summary of the changes made to this instruction manual (9289900990), BESTCOMS softwar

Page 311

Alternately, status of output contacts can be assessed at HMI Screen 1.5.2 and through the communication ports using the RG-STAT (report general-statu

Page 312 - HMI Display

Output Logic Override Control Each output contact can be controlled directly using the select-before-operate output control function. The virtual outp

Page 313 - 51 (Time Overcurrent)

2. Test all outputs by pulsing momentarily. >CS-OUT=P OUT=P SELECTED >CO-OUT=P OUT=P EXECUTED 3. Disable the trip output (

Page 314

SECTION 4 • PROTECTION AND CONTROL TABLE OF CONTENTS SECTION 4 • PROTECTION AND CONTROL ...

Page 315 - Breaker Failure

Retrieving Reclosing Status from the Relay ... 4-34 Virtual Switches

Page 316 - Logic Timers

Table 4-4. BESTlogic Settings for Instantaneous Overcurrent Protection ... 4-11 Table 4-5. Operating Settin

Page 317 - Demands

iv BE1-851 Protection and Control 9289900990 Rev R

Page 318

SECTION 4 • PROTECTION AND CONTROL Introduction BE1-851 relays provide many functions that can be used to protect and control power system equipment i

Page 319 - Fault Recording

AUTOMATIC logic input being asserted, the relay monitors loading or unbalance conditions and changes the active setting group according to the “switch

Page 320 - Inputs 1 - 4

At the top center of the BESTlogic Function Element screen is a pull-down menu labeled Logic. This menu allows viewing of the BESTlogic settings for

Page 321 - Outputs 1 – 5, A

Manual Revision and Date Change H, 09/03 • Updated the discussion on Current Measurement Functions on page 3-1 and 3-2. • In Table 4-11, changed “Di

Page 322 - Logic Select

When the setting group control function block is enabled for Discrete Inputs, there is a direct correspondence between each discrete logic input and t

Page 323 - Virtual Outputs

Figure 4-4. Input Control Binary Inputs Example 1. Make the following settings changes to the setting group control function. Set the setting grou

Page 324 - Function Blocks

At the top center of the screen is a pull-down menu labeled Logic. This menu allows viewing of the BESTlogic settings for each preprogrammed logic sc

Page 325 - Metering

group three return timer begins timing. Current varies but stays below 75 percent for 5 minutes and at time = 75, setting group two becomes active and

Page 326 - File Management

Figure 4-7. Setting Group Selection Screen Figure 4-8. Automatic Operation Based on Cold Load Pickup 4-8 BE1-851 Protection and Control 928

Page 327

Logic Override of the Setting Group Control Function Control of the active setting group from the setting group control function can be overridden. Th

Page 328 - BESTprint™

Overcurrent Protection BE1-851 overcurrent protection includes instantaneous elements for Phase, Neutral, and Negative-Sequence, as well as time overc

Page 329 - CHARACTERISTIC CURVES

Figure 4-10. BESTlogic Function Element Screen, Phase (50TP) At the top center of the BESTlogic Function Element screen is a pull-down menu labeled

Page 330

5.x.1.6 where x equals 1 for Setting Group 0, 2 for Setting Group 1, 3 for Setting Group 2, and 4 for Setting Group 3. Figure 4-11. Overcurrent Scre

Page 331

Table 4-5. Operating Settings for Instantaneous Overcurrent Protection Setting Range Increment Unit of Measure Default 1 A 5 A Pickup 0 = Disabled

Page 332

BESTCOMS™ Software Version and Date Change 2.05.00, 03/06 • Added “E”, “G”, and “R” to Case options in Style Chart Drawing. • Added Settings Compare

Page 333 - Using Table A-3

characteristic, the user can append an R to the selected time current characteristic curve. A programmable curve is available that can be used to cr

Page 334

See Section 7, BESTlogic Programmable Logic. Select Done when the settings have been completely edited. Table 4-6 summarizes the BESTlogic settings

Page 335

The pickup value determines the level of current required for the element to start timing toward a trip. Time Dial is used to select the time delay be

Page 336

Table 4-8. Definitions for Equations 4-1 and 4-2 Parameter Description Explanation TT Time to trip Time that the 51 function will take to time out an

Page 337

Programmable curve coefficients can be entered regardless of the curve chosen for the protection element. However, the programmable curve will not be

Page 338

Figure 4-17. Sequence Components for an A-B Fault Coordination Settings for Negative-Sequence Overcurrent Protection The 51Q settings should be check

Page 339

Breaker Failure Protection BF - Breaker Failure Protection BE1-851 relays provide one function block for breaker failure protection. This function inc

Page 340

An alarm variable is provided in the programmable alarms function that can be used to indicate an alarm condition when the breaker failure protection

Page 341

Example 1. Make the following BESTlogic settings to the Breaker Failure element. See Figure 4-19. Mode: Enable Initiate: VO1

Page 342

Table 4-12. Operating Settings for Breaker Failure Protection Setting Range Increment Unit of Measure Default Time 0 = Disabled N/A N/A 0 50 to

Page 343

Application Firmware Version and Date Change 3.43.09, 03/03 • Added the capability of changing Modbus Password Security with the ASCII command. • En

Page 344

Mode 1, PU/DO (Pickup/Dropout Timer) The output will change to logic TRUE if the INITIATE input expression is TRUE for the duration of PICKUP time de

Page 345

Mode 4, Oscillator In this mode, the INITIATE input is ignored. See Figure 4-25. If the BLOCK input is FALSE, the output, x62, oscillates with an ON t

Page 346

time, the function will still time out as long as the time that it is TRUE is longer than the time that it is FALSE. With a simple pickup/dropout time

Page 347

To connect the element’s inputs, select the button for the corresponding input in the BESTlogic Function Element screen. The BESTlogic Expression Bui

Page 348

At the top center of the screen is a pull-down menu labeled Logic. This menu allows viewing of the BESTlogic settings for each preprogrammed logic sc

Page 349

Inputs and Outputs Reclose Initiate (RI) The RI input is used with the 52 status input to start the reclose timers at each step of the reclosing seq

Page 350

Recloser Fail Timer (79F) This timer begins when the 79C output becomes TRUE and continues counting until the STATUS input becomes TRUE. If the 79F ti

Page 351

used. Then, select the BESTlogic variable, or series of variables to be connected to the input. Select Save when finished to return to the BESTlogic

Page 352

At the top of the screen is a pull-down menu labeled Logic. This menu allows viewing of the BESTlogic settings for each preprogrammed logic scheme. A

Page 353

Figure 4-35. S#-79SCB=1/2/3/4/5 Logic Timing Diagram Figure 4-36. S#-79SCB=2/3/4/5 Logic Timing Diagram Zone-Sequence Coordination To coordinate

Page 354

Application Firmware Version and Date Change interface using the RG-TARG=0 command. This allows targets to be reset by pulsing a contact sensing input

Page 355

Figure 4-37. BESTlogic Function Element Screen, Reclosing (Zone Sequence Logic) Table 4-17 summarizes the settings for Zone-Sequence Coordination.

Page 356

Figure 4-38. Overall Logic Diagram for Reclosing 9289900990 Rev R BE1-851 Protection and Control 4-35

Page 357

Virtual Switches 43 - Virtual Selector Switches BE1-851 relays have four virtual selector switches that can provide manual control, locally and remote

Page 358

Figure 4-40. BESTlogic Function Element Screen, 43 At the top center of the BESTlogic Function Element screen is a pull-down menu labeled Logic. Thi

Page 359

CS/CO-x43 Command Examples: Example 1. Read the current status of virtual switch 43. >CO-43 0 Example 2. Momentarily toggle t

Page 360

Figure 4-42. 101 Control Switch State Diagram When the virtual control switch is controlled to trip, the 101T output pulses TRUE (closed) for appro

Page 361

Table 4-19. BESTlogic Settings for Virtual Breaker Control Switch Function Range/Purpose Default Mode 0 = Disable, 1 = Enable 0 Example 1. Mak

Page 362

SECTION 5 • METERING TABLE OF CONTENTS SECTION 5 • METERING ...

Page 363

ii BE1-851 Metering 9289900990 Rev R

Page 364

SECTION 5 • METERING General The BE1-851 relay measures current inputs, displays those values in real time, records those values every one-quarter sec

Comments to this Manuals

No comments