Basler-electric BE1-50/51B-244 User Manual

Browse online or download User Manual for Relay Basler-electric BE1-50/51B-244. Basler Electric BE1-50/51B-244 User Manual

  • Download
  • Add to my manuals
  • Print

Summary of Contents

Page 1 - INSTRUCTION MANUAL

INSTRUCTION MANUAL FOR OVERCURRENT RELAYS BE1-50/51B-244 Publication: 9252000793 Revision: C 12/11 ACTIVE/PICKUPPICKUP(0.5 MIN. SET)TIME DIALTENTH

Page 2

ii BE1-50/51B-244 General Information 9252000793 Rev C

Page 3 - INTRODUCTION

9252000793 Rev C BE1-50/51B-244 General Information 1-1 SECTION 1 • GENERAL INFORMATION Introduction BE1-50/51B-244 protective relays are direct re

Page 4 - HIGHLAND IL 62249 USA

1-2 BE1-50/51B-244 General Information 9252000793 Rev C Westinghouse CO type curves, and instantaneous or integrating reset characteristics. Switch

Page 5 - REVISION HISTORY

9252000793 Rev C BE1-50/51B-244 General Information 1-3 Switch selectable—no intentional delay (SW3-2 OFF) or a fixed delay of 100 ms (SW3-2 ON). Ap

Page 6

1-4 BE1-50/51B-244 General Information 9252000793 Rev C Figure 1-2. Current Sensing Input Burden (BE1-50/51B-244) Frequency Response A change of ±

Page 7 - CONTENTS

9252000793 Rev C BE1-50/51B-244 General Information 1-5 Target Indicators A gravity-latched, manually-reset, current-operated target indicator is pr

Page 8

1-6 BE1-50/51B-244 General Information 9252000793 Rev C

Page 9

9252000793 Rev C BE1-50/51B-244 Controls and Indicators i SECTION 2 • CONTROLS AND INDICATORS TABLE OF CONTENTS SECTION 2 • CONTROLS AND INDICATORS

Page 10

ii BE1-50/51B-244 Controls and Indicators 9252000793 Rev C

Page 11 - Features

9252000793 Rev C BE1-50/51B-244 Controls and Indicators 2-1 SECTION 2 • CONTROLS AND INDICATORS Introduction BE1-50/51B-244 relay controls and indic

Page 13 - Current (Aac)

2-2 BE1-50/51B-244 Controls and Indicators 9252000793 Rev C Table 2-1. Front Panel Controls and Indicators Locator Description A Instantaneous Overc

Page 14 - BE1-50/51B-244 CT Burden

9252000793 Rev C BE1-50/51B-244 Controls and Indicators 2-3 Circuit Board Controls Circuit board controls consist of two rotary selector switches, a

Page 15

2-4 BE1-50/51B-244 Controls and Indicators 9252000793 Rev C Table 2-2. Circuit Board Controls Locator Description A Target Operating Current Jumpers

Page 16

9252000793 Rev C BE1-50/51B-244 Functional Description i SECTION 3 • FUNCTIONAL DESCRIPTION TABLE OF CONTENTS SECTION 3 • FUNCTIONAL DESCRIPTION ..

Page 17 - TABLE OF CONTENTS

ii BE1-50/51B-244 Functional Description 9252000793 Rev C

Page 18

9252000793 Rev C BE1-50/51B-244 Functional Description 3-1 SECTION 3 • FUNCTIONAL DESCRIPTION Introduction This section illustrates and describes th

Page 19

3-2 BE1-50/51B-244 Functional Description 9252000793 Rev C RC time constant. This provides information from the integrating reset function even when

Page 20

9252000793 Rev C BE1-50/51B-244 Installation i SECTION 4 • INSTALLATION TABLE OF CONTENTS SECTION 4 • INSTALLATION ...

Page 21 - P0064-45

ii BE1-50/51B-244 Installation 9252000793 Rev C

Page 22

9252000793 Rev C BE1-50/51B-244 Installation 4-1 SECTION 4 • INSTALLATION General When not shipped as part of a control or switchgear panel, the rel

Page 23

9252000793 Rev C BE1-50/51B-244 Introduction i INTRODUCTION This instruction manual provides information about the operation and installation of the

Page 24

4-2 BE1-50/51B-244 Installation 9252000793 Rev C Figure 4-2. Outline Dimensions, FT11 Case Figure 4-3. Outline Dimensions, FT21 Case Factory Sett

Page 25

9252000793 Rev C BE1-50/51B-244 Installation 4-3 Installation Select the desired relay settings before putting the relay into service. Changing pick

Page 26 - Outputs

4-4 BE1-50/51B-244 Installation 9252000793 Rev C Figure 4-5. Typical DC Connections Figure 4-6. Terminal Connections, Rear View 150-A51S SHORT IN

Page 27 - SECTION 4 • INSTALLATION

9252000793 Rev C BE1-50/51B-244 Installation 4-5 Application Coordination In a typical application coordination scheme, a BE1-50/51B-244 is used to

Page 28

4-6 BE1-50/51B-244 Installation 9252000793 Rev C Maintenance BE1-50/51B-244 relays require no preventative maintenance other than periodic checking

Page 29 - P0064-39

9252000793 Rev C BE1-50/51B-244 Testing i SECTION 5 • TESTING TABLE OF CONTENTS SECTION 5 • TESTING ...

Page 30 - Factory Settings

ii BE1-50/51B-244 Testing 9252000793 Rev C

Page 31 - Connections

9252000793 Rev C BE1-50/51B-244 Testing 5-1 SECTION 5 • TESTING Introduction Proper relay operation may be confirmed by performing the test procedur

Page 32 - OVERCURRENT

5-2 BE1-50/51B-244 Testing 9252000793 Rev C 2. Apply and increase current to terminals 8 and 9 until the Active/Pickup LED turns red. The applied c

Page 33 - Application Coordination

9252000793 Rev C BE1-50/51B-244 Testing 5-3 1. Connect and configure the relay for 50-A pickup testing: Instantaneous Overcurrent A (50-A) Pickup a

Page 34 - Storage

ii BE1-50/51B-244 Introduction 9252000793 Rev C First Printing: March 2011 Printed in USA © 2011 Basler Electric, Highland Illinois 62249 USA All R

Page 35 - SECTION 5 • TESTING

5-4 BE1-50/51B-244 Testing 9252000793 Rev C f. Set INST PICKUP (50-A) to 90. g. Set INST PICKUP (50-B) (accessed at the top side of the assembly)

Page 36

9252000793 Rev C BE1-50/51B-244 Testing 5-5 8. Slowly increase the voltage source to provide target current and verify that the Instantaneous targe

Page 37

5-6 BE1-50/51B-244 Testing 9252000793 Rev C

Page 38 - Integrating Reset

9252000793 Rev C BE1-50/51B-244 Characteristic Curves i APPENDIX A • CHARACTERISTIC CURVES TABLE OF CONTENTS APPENDIX A • CHARACTERISTIC CURVES ...

Page 39

ii BE1-50/51B-244 Characteristic Curves 9252000793 Rev C

Page 40

9252000793 Rev C BE1-50/51B-244 Characteristic Curves A-1 APPENDIX A • CHARACTERISTIC CURVES Introduction This appendix describes and defines the in

Page 41 - Manual Trip

A-2 BE1-50/51B-244 Characteristic Curves 9252000793 Rev C Inverse Time Functions Characteristic curves for the inverse and definite time functions a

Page 42

9252000793 Rev C BE1-50/51B-244 Characteristic Curves A-3 Figures A-2 through A-15 illustrate the BE1-50/51B-244 time overcurrent characteristic cur

Page 43

A-4 BE1-50/51B-244 Characteristic Curves 9252000793 Rev C Figure A-3. Long Inverse (L) Time Characteristic Curve (SW3-3 Off, Similar to ABB CO-5)

Page 44

9252000793 Rev C BE1-50/51B-244 Characteristic Curves A-5 Figure A-4. Definite Time (D) Time Characteristic Curve (Similar to ABB CO-6)

Page 45

9252000793 Rev C BE1-50/51B-244 Introduction iii REVISION HISTORY The following information provides a historical summary of the changes made to thi

Page 46 - Characteristic Curve Groups

A-6 BE1-50/51B-244 Characteristic Curves 9252000793 Rev C Figure A-5. Moderately Inverse (M) Time Characteristic Curve (Similar to ABB CO-7)

Page 47 - Characteristic Curves

9252000793 Rev C BE1-50/51B-244 Characteristic Curves A-7 Figure A-6. Inverse (I) Time Characteristic Curve (SW3-3 Off, Similar to ABB CO-8)

Page 48

A-8 BE1-50/51B-244 Characteristic Curves 9252000793 Rev C Figure A-7. Very Inverse (V) Time Characteristic Curve (SW3-3 Off, Similar to ABB CO-9)

Page 49

9252000793 Rev C BE1-50/51B-244 Characteristic Curves A-9 Figure A-8. Extremely Inverse (E) Time Characteristic Curve (SW3-3 Off, Similar to ABB CO

Page 50

A-10 BE1-50/51B-244 Characteristic Curves 9252000793 Rev C Figure A-9. BS142 Very Inverse (BS142-B) Time Characteristic Curve

Page 51

9252000793 Rev C BE1-50/51B-244 Characteristic Curves A-11 Figure A-10. BS142 Extremely Inverse (BS142-C) Time Characteristic Curve

Page 52

A-12 BE1-50/51B-244 Characteristic Curves 9252000793 Rev C Figure A-11. Short Inverse (S2) Time Characteristic Curve (SW3-3 On, Similar to GE IAC 5

Page 53

9252000793 Rev C BE1-50/51B-244 Characteristic Curves A-13 Figure A-12. Long Inverse (L2) Time Characteristic Curve (SW3-3 On, Similar to GE IAC 66

Page 54

A-14 BE1-50/51B-244 Characteristic Curves 9252000793 Rev C Figure A-13. Inverse (I2) Time Characteristic Curve (SW3-3 On, Similar to GE IAC 51)

Page 55

9252000793 Rev C BE1-50/51B-244 Characteristic Curves A-15 Figure A-14. Very Inverse (V2) Time Characteristic Curve (SW3-3 On, Similar to GE IAC 53

Page 56

iv BE1-50/51B-244 Introduction 9252000793 Rev C

Page 57

A-16 BE1-50/51B-244 Characteristic Curves 9252000793 Rev C Figure A-15. Extremely Inverse (E2) Time Characteristic Curve (SW3-3 On, Similar to GE I

Page 58

9252000793 Rev C BE1-50/51B-244 Characteristic Curves A-17 Timing Accuracy Timing accuracy is the sum of ±1 cycle, ±2%. This accuracy applies to the

Page 59

A-18 BE1-50/51B-244 Characteristic Curves 9252000793 Rev C Reset occurs within 16 ms of when the current decreases to 95% of the pickup level. Insta

Page 61 - Fixed Time Characteristic

12570 State Route 143Highland IL 62249-1074 USAwww.basler.com, [email protected] +1 618.654.2341 Fax +1 618.654.2351®

Page 62 - Instantaneous Reset

9252000793 Rev C BE1-50/51B-244 Introduction v CONTENTS SECTION 1 • GENERAL INFORMATION ...

Page 63

vi BE1-50/51B-244 Introduction 9252000793 Rev C

Page 64 - Highland IL 62249-1074 USA

9252000793 Rev C BE1-50/51B-244 General Information i SECTION 1 • GENERAL INFORMATION TABLE OF CONTENTS SECTION 1 • GENERAL INFORMATION ....

Comments to this Manuals