Page 1 - INSTRUCTION MANUAL

INSTRUCTION MANUAL FOR BE1-50/51B OVERCURRENT RELAY Part Numbers 9252000122 Publication: 9252000997 Revision:

Page 2

vi BE1-50/51B-219/-226 Introduction 9252000981 Rev H This page intentionally left blank.

Page 3

9252000981 Rev H BE1-50/51B-219/-226 General Information i SECTION 1  GENERAL INFORMATION TABLE OF CONTENTS SECTION 1  GENERAL INFORMATION ...

Page 4

ii BE1-50/51B-219/-226 General Information 9252000981 Rev H This page intentionally left blank.

Page 5

9252000981 Rev H BE1-50/51B-219/-226 General Information 1-1 SECTION 1  GENERAL INFORMATION INTRODUCTION BE1-50/51B-219 and BE1-50/51B-226 protecti

Page 6 - HIGHLAND IL 62249 USA

1-2 BE1-50/51B-219/-226 General Information 9252000981 Rev H type curves, and instantaneous or integrating reset characteristics. Switch location an

Page 7 - REVISION HISTORY

Timing Accuracy Example (BE1-50/51B-219) PU setting: 5 amperes Current Applied: 6.5 amperes + Multiple Tolerance: 6.655 amperes – Multiple Tol

Page 8

Table 1-3. Time Characteristic Curve Constants with SW3-3 Closed (On) Curve Type  Constants BE1 Similar To Figure Number † A B C N K R S GE IAC 55

Page 9 - CONTENTS

1.010.0100.00.000 0.200 0.400 0.600 0.800 1.000 1.200Multiple of PickupxRD (Seconds)P0046-11Vertical axis xRD (Seconds) is applicable for all curves a

Page 10

Figure 1-2. Instantaneous Characteristic Curves Burden Burden is non-linear. Figure 1-3 illustrates the device burden. BE1-50/51B-219 At 0.5 amperes

Page 11 - TABLE OF CONTENTS

Figure 1-3. Burden Characteristics Frequency Response A change of ±5 Hz from the nominal 50/60 Hz current causes <0.5% change in the current requ

Page 13 - FEATURES

Figure 1-4. Harmonic Rejection Target Indicators Gravity latched, manually reset targets indicate that current of 0.2 amperes or greater was present

Page 14 - SPECIFICATIONS

9252000981 Rev H BE1-50/51B-219/-226 General Information 1-9 Radio Frequency Interference (RFI) Field-tested using a 5-watt, hand-held transceiver o

Page 15

1-10 BE1-50/51B-219/-226 General Information 9252000981 Rev H This page intentionally left blank.

Page 16

9252000981 Rev H BE1-50/51B-219/-226 Controls and Indicators i SECTION 2  CONTROLS AND INDICATORS TABLE OF CONTENTS SECTION 2  CONTROLS AND INDIC

Page 17 - P0046-11

ii BE1-50/51B-219/-226 Controls and Indicators 9252000981 Rev H This page intentionally left blank.

Page 18

SECTION 2  CONTROLS AND INDICATORS INTRODUCTION Figure 2-1 illustrates the front panel controls and indicators of the BE1-50/51B-219 and BE1-50/51B-2

Page 19

P0053-50SW3 Figure 2-2. Location of SW3 2-2 BE1-50/51B-219/-226 Controls and Indicators 9252000981 Rev H

Page 20

9252000981 Rev H BE1-50/51B-219/-226 Controls and Indicators 2-3 Table 2-1. BE1-50/51B-219 and BE1-50/51B-226 Controls and Indicators (Refer to Figu

Page 21

2-4 BE1-50/51B-219/-226 Controls and Indicators 9252000981 Rev H This page intentionally left blank.

Page 22

9252000981 Rev H BE1-50/51B-219/-226 Functional Description i SECTION 3  FUNCTIONAL DESCRIPTION TABLE OF CONTENTS SECTION 3  FUNCTIONAL DESCRIPTI

Page 23

A-1 9252000997 First Printing: August 2010 Printed in USA Copyright © 2010 Basler Electric, Highland Illinois USA INTRODUTION This manual, publicatio

Page 24

ii BE1-50/51B-219/-226 Functional Description 9252000981 Rev H This page intentionally left blank.

Page 25

9252000981 Rev H BE1-50/51B-219/-226 Functional Description 3-1 SECTION 3  FUNCTIONAL DESCRIPTION GENERAL BE1-50/51B-219 and BE1-50/51B-226 Overcur

Page 26 - P0053-50

Outputs Instantaneous and Timed System circuit breakers controlled by the output contacts can be manually tripped by applying a short across the TIME

Page 27

9252000981 Rev H BE1-50/51B-219/-226 Installation i SECTION 4  INSTALLATION TABLE OF CONTENTS SECTION 4  INSTALLATION ...

Page 28

ii BE1-50/51B-219/-226 Installation 9252000981 Rev H This page intentionally left blank.

Page 29

SECTION 4  INSTALLATION GENERAL When not shipped as part of a control or switchgear panel, the relays are shipped in sturdy cartons to prevent damage

Page 30

From the time characteristic curve equation. KBDCMADTNTrip 0280202758.011027624709382... 028005516.0110806124524815... seconds 0.209

Page 31 - FUNCTIONAL DESCRIPTION

Equation for time to trip during rewind (before relay is reset). Rewind FullTime RewindTrip FullTOccurence This Trip Second Operation 15.530

Page 32

Figure 4-3. DC Control Connections MAINTENANCE BE1-50/51B-219 and BE1-50/51B-226 overcurrent relays require no preventive maintenance. However, peri

Page 33 - SECTION 4  INSTALLATION

9252000981 Rev H BE1-50/51B-219/-226 Testing i SECTION 5  TESTING TABLE OF CONTENTS SECTION 5  TESTING ...

Page 34

This page intentionally left blank.

Page 35

ii BE1-50/51B-219/-226 Testing 9252000981 Rev H This page intentionally left blank.

Page 36

SECTION 5  TESTING GENERAL Dielectric testing, operational testing, and periodic testing are described in the following paragraphs. DIELECTRIC TEST I

Page 37 - CONNECTIONS

Figure 5-1. Pickup and Timing Test Setup BE1-50/51B-21989 1 2TIME INST10CURRENTSOURCEINPUTSTOPTIMERSTARTAMPSTEST SETP0057-19RAC or DCVoltageSource

Page 38 - STORAGE

NOTE When testing TIME overcurrent functions, INST PICKUP settings of 00 will affect the calibration of the TIME functions. TIME PICKUP settings of 00

Page 39 - SECTION 5  TESTING

Step 1. Prepare to apply 1.5 amperes input current to terminals 8 and 9 and record the elapsed time from when current is applied until TIME

Page 40

9252000981 Rev H BE1-50/51B-219/-226 Testing 5-5 Integrating Reset Test Perform preliminary setup:  Connect test setup as shown in Figure 5-1. 

Page 41

Time Dial Test Perform preliminary setup:  Connect test setup as shown in Figure 5-1.  Insure that SW3 switches are set: SW3-1 for the operating f

Page 42 - P0057-19

9252000981 Rev H BE1-50/51B-219/-226 Testing 5-7 Step 3. Connect a jumper between TIME MANUAL TRIP test points. Check that TIME target operates. St

Page 43

5-8 BE1-50/51B-219/-226 Testing 9252000981 Rev H This page intentionally left blank.

Page 44

9252000981 Rev H BE1-50/51B-219/-226 Time Characteristic Curves i APPENDIX A  TIME CHARACTERISTIC CURVES TABLE OF CONTENTS APPENDIX A  TIME CHARA

Page 45

INTRODUCTION This instruction manual provides information about the operation and installation of the BE1-50/51B-219 and BE1-50/51B-226 Overcurrent Re

Page 46

ii BE1-50/51B-219/-226 Time Characteristic Curves 9252000981 Rev H This page intentionally left blank.

Page 47 - PERIODIC TESTS

APPENDIX A  TIME CHARACTERISTIC CURVES TIME CHARACTERISTIC CURVES Figures A-1 through A-14 illustrate the time characteristic curves that are program

Page 48

Figure A-2. Time Characteristic Curve, L-Long Inverse (SW3-3 OFF, Similar to ABB CO-5) A-2 BE1-50/51B-219/-226 Time Characteristic Curves 925200098

Page 49

Figure A-3. Time Characteristic Curve, D-Definite Time (Similar to ABB CO-6) 9252000981 Rev H BE1-50/51B-219/-226 Time Characteristic Curves A-3

Page 50

Figure A-4. Time Characteristic Curve, M-Moderately Inverse (Similar to ABB CO-7) A-4 BE1-50/51B-219/-226 Time Characteristic Curves 9252000981 Rev

Page 51 - TIME CHARACTERISTIC CURVES

Figure A-5. Time Characteristic Curve, I-Inverse (SW3-3 OFF, Similar to ABB CO-8) 9252000981 Rev H BE1-50/51B-219/-226 Time Characteristic Curves

Page 52

Figure A-6. Time Characteristic Curve, V-Very Inverse (SW3-3 OFF, Similar to ABB CO-9) A-6 BE1-50/51B-219/-226 Time Characteristic Curves 92520009

Page 53 - (Similar to ABB CO-6)

Figure A-7. Time Characteristic Curve, E-Extremely Inverse (SW3-3 OFF, Similar to ABB CO-11) 9252000981 Rev H BE1-50/51B-219/-226 Time Characteristi

Page 54 - (Similar to ABB CO-7)

Figure A-8. Time Characteristic Curve, BS142-B (BS142 Very Inverse) A-8 BE1-50/51B-219/-226 Time Characteristic Curves 9252000981 Rev H

Page 55

Figure A-9. Time Characteristic Curve, BS142-C (BS142 Extremely Inverse) 9252000981 Rev H BE1-50/51B-219/-226 Time Characteristic Curves A-9

Page 56

First Printing: June 1996 Printed in USA © 2009 Basler Electric, Highland Illinois 62249 USA All Rights Reserved January 2009 CONFIDENTIAL INF

Page 57

Figure A-10. Time Characteristic Curve, S2-Short Inverse (SW3-3 ON, Similar to GE IAC 55) A-10 BE1-50/51B-219/-226 Time Characteristic Curves 92520

Page 58

Figure A-11. Time Characteristic Curve, L2-Long Inverse (SW3-3 ON, Similar to GE IAC 66) 9252000981 Rev H BE1-50/51B-219/-226 Time Characteristic Cu

Page 59 - (BS142 Extremely Inverse)

Figure A-12. Time Characteristic Curve, I2-Inverse (SW3-3 ON, Similar to GE IAC 51) A-12 BE1-50/51B-219/-226 Time Characteristic Curves 9252000981

Page 60

Figure A-13. Time Characteristic Curve, V2-Very Inverse (SW3-3 ON, Similar to GE IAC 53) 9252000981 Rev H BE1-50/51B-219/-226 Time Characteristic Cu

Page 61

Figure A-14. Time Characteristic Curve, E2-Extremely Inverse (SW3-3 ON, Similar to GE IAC 77) A-14 BE1-50/51B-219/-226 Time Characteristic Curves 9

Page 63

ROUTE 143, BOX 269 HIGHLAND, IL 62249 USA http://www.basler.com, [email protected] PHONE +1 618-654-2

Page 64

9252000981 Rev H BE1-50/51B-219/-226 Introduction iii REVISION HISTORY The following information provides a historical summary of the changes made t

Page 65

iv BE1-50/51B-219/-226 Introduction 9252000981 Rev H This page intentionally left blank.

Page 66

9252000981 Rev H BE1-50/51B-219/-226 Introduction v CONTENTS SECTION 1  GENERAL INFORMATION ..............