216 9369700990 Rev R
Holding Registers for System Configuration
Table 37. Information Category C3System Configuration
Registers
Data Description
Access
Data
Format
40401
Sensing Configuration
RW
UINT16
40402
Auxiliary Input Summing Mode
RW
UINT16
40403
Bridge Control Signal
RW
UINT16
40404
Generator Field Type
RW
UINT16
40405
Voltage Sensing H/W Gain Control
R
UINT16
40406
Auxiliary Input Type
RW
UINT16
40407
Temperature Mode
RW
UINT16
40408
Number of CT's
RW
UINT16
40409
Selected CT's
RW
UINT16
40410
Motor/Generator Mode
R
UINT16
40411
Auxiliary Input Function; 0=DECS, 1=PSS, 2=LIMITER, 3=METONLY
RW
UINT16
40412 to
40450
Reserved for future C3 use
R
Not
Defined
40451
Rated Generator Frequency
RW
FLOAT
40453
Generator PT Primary Voltage
RW
FLOAT
40455
Generator PT Secondary Voltage
RW
FLOAT
40457
Generator CT Primary Current
RW
FLOAT
40459
Generator CT Secondary Current
RW
FLOAT
40461
Field Current Shunt Rating
RW
FLOAT
40463
Field Voltage Isolation Module Input
RW
FLOAT
40465
Bus PT Primary Voltage
RW
FLOAT
40467
Bus PT Secondary Voltage
RW
FLOAT
40469
Maximum Field Flash Time
RW
FLOAT
40471
Field Flash Dropout Level
RW
FLOAT
40473
Generator Rated Voltage
RW
FLOAT
40475
Generator Rated kVA
RW
FLOAT
40477
Generator Rated Field Voltage
RW
FLOAT
40479
Generator Rated Field Current
RW
FLOAT
40481
Bus Voltage
RW
FLOAT
40483
Auxiliary Voltage Input Gain
RW
FLOAT
40485
Internal Tracking Time Delay
RW
FLOAT
40487
Internal Tracking Traverse Rate
RW
FLOAT
40489
Reserved
40491
Auxiliary Current Input Gain
RW
FLOAT
40493
External Tracking Time Delay
RW
FLOAT
40495
External Tracking Traverse Rate
RW
FLOAT
40497
Auxiliary Input Gain for FCR Mode
RW
FLOAT
40499
Auxiliary Input Gain for VAR Mode
RW
FLOAT
40501
Auxiliary Input Gain for PF Mode
RW
FLOAT
40503
Exciter Field Resistance
RW
FLOAT
40505
Ambient Temperature
RW
FLOAT
40507
Brush Voltage Drop
RW
FLOAT
40509
Generator Power Factor
RW
FLOAT
40511
Auxiliary Input Gain for FVR Mode
RW
FLOAT
40513 to
40599
Reserved for future C3 use
R
Not
Defined
Modbus™ Communication DECS-400