9369700990 Rev R 163
Traverse Rate
Range ............................................ 1 to 80 s
Increment ...................................... 0.1 s
Soft Start
Two sets of soft start settings are available when operating in AVR or FCR mode.
Soft Start Bias Level
Range ............................................ 0 to 90%
Increment ...................................... 1%
Soft Start Time Delay
Range ............................................ 1 to 7,200 s
Increment ...................................... 1 s
Sequence of Events Recording
Events are time- and date-stamped and stored in volatile memory.
Event Capacity .............................. 127
Scan Interval ................................. 50 ms
Logic Triggers……………………... Input state change, output state change, alarm annunciation, or system
operating status change
Data Logging (Oscillography)
Record Capacity ............................ 6
Variables per Record .................... 6
Sampling Rate ............................... 600 data points per record
Pre-Trigger Points ......................... Up to 599
Record Duration ............................ 2.4 s to 6,000 s
Interval ........................................... 4 ms to 10 s
Trending
Record Capacity ............................ 1
Variables per Record .................... 6
Sampling Rate ............................... 1,200 data points per record
Record Duration ............................ 1 hr to 30 d
Limiters
Underfrequency Compensation
Slope Adjustment Range .............. 0 to 0.3 PU
Knee Frequency Range ................ 15 to 90 Hz
Volts per Hertz
Slope Adjustment Range .............. 0 to 3 PU
Time Delay Range ........................ 0 to 10 s