INSTRUCTION MANUAL FOR BE1-50/51B-240 Overcurrent Relay Publication: 9252000790 Revision: B 08/14

Page 2

2 9252000790 Rev B • Built-in accuracy eliminates internal adjustments • Minimum transient overreach • Field selectable characteristic curve sel

Page 3 - Preface

9252000790 Rev B 3 Reset Integrating: Simulates the disk reset of electromechanical relays and begins when the current decreases below 95% of pickup

Page 4

4 9252000790 Rev B Figure 2. Current Sensing Input Burden Frequency Response A change of ±5 Hz from the nominal 50/60 Hz current causes <0.5% c

Page 5 - Revision History

9252000790 Rev B 5 Target Indicators A gravity-latched, manually-reset, current-operated target indicator is provided for the time-overcurrent (51) t

Page 6 - 9252000790 Rev B

6 9252000790 Rev B General Information BE1-50/51B-240

Page 7 - Contents

9252000790 Rev B 7 Controls and Indicators Introduction BE1-50/51B-240 relay controls and indicators are located on the front panel and circuit board

Page 8

8 9252000790 Rev B Table 2. Front Panel Controls and Indicators Locator Description A Time Overcurrent Time Dial Selector Switches. These two rotar

Page 9 - General Information

9252000790 Rev B 9 Figure 5. Circuit Board Controls Table 3. Circuit Board Controls Locator Description A Target Operating Current Jumpers. Two use

Page 10 - Specifications

10 9252000790 Rev B Locator Description C SW9 and SW10. These switches and associated instantaneous overcurrent (50-B) element are NOT used on the

Page 11 - Current Sensing Input

9252000790 Rev B 11 Functional Description Introduction This chapter illustrates and describes the functional capabilities of the BE1-50/51B-240 rela

Page 13 - Physical

12 9252000790 Rev B When sufficient current is sensed by the relay, the microprocessor is active and executing code, and the Active/Pickup LED is g

Page 14 - 6 9252000790 Rev B

9252000790 Rev B 13 Installation General When not shipped as part of a control or switchgear panel, the relays are shipped in sturdy cartons to preve

Page 15 - Controls and Indicators

14 9252000790 Rev B Connections Typical ac connections are shown in Figure 7 and typical dc connections are shown in Figure 8. Figure 7. Typical

Page 16 - Circuit Board Controls

9252000790 Rev B 15 Figure 8. Typical DC Connections Application Coordination In a typical application coordination scheme, a BE1-50/51B-240 is used

Page 17

16 9252000790 Rev B From the reset characteristic curve equation: 12−=MRDTR M equals 0 if current goes to zero. A negative result indicates reset t

Page 18

9252000790 Rev B 17 Testing Introduction Proper relay operation may be confirmed by performing the test procedures in this chapter. Dielectric Test I

Page 19 - Functional Description

18 9252000790 Rev B Figure 10. 51 Pickup, Time Dial, Integrating Reset, 50 Pickup, and Manual Trip Test Setup Time Dial 1. Connect and configure

Page 20 - Warning!

9252000790 Rev B 19 c. Set TIME DIAL to 9.9 d. Set CURVE to V. e. Set TIME PICKUP to 1.0. f. Set INST PICKUP to 90. 2. Apply 4.0 Aac to terminal

Page 21 - Installation

20 9252000790 Rev B 4. Remove the jumper and the current applied at relay terminals 8 and 9. 5. Apply 0.9 Aac to terminals 8 and 9. 6. Connect a

Page 22 - Connections

9252000790 Rev B 21 Figure 11. Target Indicators Test Setup BE1-50/51B-240 Testing

Page 23 - Application Coordination

9252000790 Rev B i Preface This instruction manual provides information about the installation and operation of the BE1-50/51B-240 Overcurrent Relay.

Page 24 - Storage

22 9252000790 Rev B Testing BE1-50/51B-240

Page 25 - Testing

9252000790 Rev B 23 Characteristic Curves Introduction This chapter describes and defines the instantaneous overcurrent, time overcurrent, and integr

Page 26 - Integrating Reset

24 9252000790 Rev B Time Overcurrent Characteristics Nine inverse time functions and one fixed (definite) time function can be selected at the fron

Page 27 - Manual Trip

9252000790 Rev B 25 Table 5. Time Characteristic Curve Constants with Switch SW3-3 Closed (On) Curve Type Similar To Figure Number Constants BE A B C

Page 28

26 9252000790 Rev B Figure 13. Short Inverse (S) Time Characteristic Curve (SW3-3 Off, Similar to CO-2) Characteristic Curves BE1-50/51B-240

Page 29

9252000790 Rev B 27 Figure 14. Long Inverse (L) Time Characteristic Curve (SW3-3 Off, Similar to CO-5) BE1-50/51B-240 Characteristic Curves

Page 30 - Testing BE1-50/51B-240

28 9252000790 Rev B Figure 15. Definite Time (D) Time Characteristic Curve (Similar to CO-6) Characteristic Curves BE1-50/51B-240

Page 31 - Characteristic Curves

9252000790 Rev B 29 Figure 16. Moderately Inverse (M) Time Characteristic Curve (Similar to CO-7) BE1-50/51B-240 Characteristic Curves

Page 32 - Characteristic Curve Groups

30 9252000790 Rev B Figure 17. Inverse (I) Time Characteristic Curve (SW3-3 Off, Similar to CO-8) Characteristic Curves BE1-50/51B-240

Page 33

9252000790 Rev B 31 Figure 18. Very Inverse (V) Time Characteristic Curve (SW3-3 Off, Similar to CO-9) BE1-50/51B-240 Characteristic Curves

Page 34 - 26 9252000790 Rev B

ii 9252000790 Rev B 12570 State Route 143 Highland IL 62249-1074 USA www.basler.com [email protected] Tel: +1 618.654.2341 Fax: +1 618.654.2351

Page 35 - 9252000790 Rev B 27

32 9252000790 Rev B Figure 19. Extremely Inverse (E) Time Characteristic Curve (SW3-3 Off, Similar to CO-11) Characteristic Curves BE1-50/51B-2

Page 36 - 28 9252000790 Rev B

9252000790 Rev B 33 Figure 20. BS142 Very Inverse (BS142-B) Time Characteristic Curve BE1-50/51B-240 Characteristic Curves

Page 37 - 9252000790 Rev B 29

34 9252000790 Rev B Figure 21. BS142 Extremely Inverse (BS142-C) Time Characteristic Curve Characteristic Curves BE1-50/51B-240

Page 38 - 30 9252000790 Rev B

9252000790 Rev B 35 Figure 22. Short Inverse (S2) Time Characteristic Curve (SW3-3 On, Similar to IAC 55) BE1-50/51B-240 Characteristic Curves

Page 39 - 9252000790 Rev B 31

36 9252000790 Rev B Figure 23. Long Inverse (L2) Time Characteristic Curve (SW3-3 On, Similar to IAC 66) Characteristic Curves BE1-50/51B-240

Page 40 - 32 9252000790 Rev B

9252000790 Rev B 37 Figure 24. Inverse (I2) Time Characteristic Curve (SW3-3 On, Similar to IAC 51) BE1-50/51B-240 Characteristic Curves

Page 41 - 9252000790 Rev B 33

38 9252000790 Rev B Figure 25. Very Inverse (V2) Time Characteristic Curve (SW3-3 On, Similar to IAC 53) Characteristic Curves BE1-50/51B-240

Page 42 - 34 9252000790 Rev B

9252000790 Rev B 39 Figure 26. Extremely Inverse (E2) Time Characteristic Curve (SW3-3 On, Similar to IAC 77) BE1-50/51B-240 Characteristic Curves

Page 43 - 9252000790 Rev B 35

40 9252000790 Rev B Timing Accuracy Timing accuracy is the sum of ±1 cycle, ±2%. This accuracy applies to the range of 1.3 to 40 times tap and is f

Page 44 - 36 9252000790 Rev B

9252000790 Rev B 41 Reset characteristic curve equation: Reset to TimeMRDTR=−=12 Instantaneous Reset Reset occurs within 16 milliseconds of when the

Page 45 - 9252000790 Rev B 37

9252000790 Rev B iii Revision History The following information provides a historical summary of the changes made to this instruction manual (9252000

Page 46 - 38 9252000790 Rev B

42 9252000790 Rev B Characteristic Curves BE1-50/51B-240

Page 48 - Fixed Time Characteristic

12570 State Route 143 Highland IL 62249-1074 USA Tel: +1 618.654.2341 Fax: +1 618.654.2351 email: [email protected] P.A.E. Les Pins 67319 Wasselonne

Page 49

iv 9252000790 Rev B Revision History Overcurrent Relay

Page 50 - 42 9252000790 Rev B

9252000790 Rev B v Contents General Information ...

Page 51

vi 9252000790 Rev B Contents Overcurrent Relay

Page 52

9252000790 Rev B 1 General Information Introduction The BE1-50/51B-240 protective relay is a direct replacement for ABB/Westinghouse type CO relays h